| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 72 mm |
| Width | 12.5 mm |
| Depth | 71.3 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Range compatibility | TeSys Deca LC1D09…95 AC coil; TeSys Deca LC1D40A…80A AC Coil; TeSys Deca LC1D115/150; TeSys Deca CAD AC coil; TeSys F LC1F |
| Mounting location | Side |
| Pole contact composition | 2 NO |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.900 cm |
| Package 1 Width | 7.300 cm |
| Package 1 Length | 8.200 cm |
| Package 1 Weight | 60.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 60 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.080 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 960 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 80.000 kg |
The auxiliary switch block LAD8N20 from the TeSys series by Schneider Electric is an undelayed auxiliary switch module specifically designed for mounting on TeSys Deca contactors. It serves as an additional component to extend control and signal transmission functions in industrial systems. The block features two closing contacts (2S) and is mounted laterally to the main component, with terminals front-mounted and snap-in. The screw terminals allow for a secure and reliable connection with flexible or rigid cables in cross-sections from 1 to 4 mm², with or without wire end ferrules. The tightening torque is 1.7 Nm, and installation is performed using a flat-head screwdriver (Ø 6) or a Phillips screwdriver (No. 2).
Applications
The auxiliary switch block is used in industrial control systems where additional switching functions are required for operational monitoring, signal transmission, or feedback of switching states. It is compatible with various TeSys Deca contactor models, including LC1D09 to LC1D95 with AC coil, LC1D40A to LC1D80A with AC coil, LC1D115/150, CAD AC coil, and LC1F. It is intended for use in installations under normal ambient conditions, with an operating temperature range of -5 to 60 °C and a storage temperature range of -60 to 80 °C. The maximum operating altitude is 3,000 m above sea level.
Functions and Equipment in Detail
The block is designed for undelayed switching operations, with contacts switching without delay. The non-overlapping time is 1.5 ms, both during energizing and de-energizing, ensuring precise and reliable switching sequences. The mechanical life is 30 million switching cycles, enabling high operational reliability in demanding applications. The minimum switching current is 5 mA, and the minimum switching voltage is 17 V, allowing use even with weak signals. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation and safety.
Technology Explained Simply
The auxiliary switch block is rated for operating voltages up to 690 V AC (25–400 Hz) and has a rated insulation voltage of 690 V (according to IEC 60947-5-1), 600 V (UL), and 600 V (CSA). The operating rated currents are 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The conventional thermal current is 10 A at 60 °C in free air. The permissible short-time current is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms. The rated switching capacity is 140 A AC and 250 A DC according to IEC 60947-5-1. The protection class IP20 corresponds to IEC 60529 and protects against finger contact, but not against dust or water. The coating corresponds to TH class according to IEC 60068.
Compatibility and Accessories
The auxiliary switch block is specifically designed for use with TeSys Deca contactors, particularly models LC1D09 to LC1D95 with AC coil, LC1D40A to LC1D80A with AC coil, LC1D115/150, CAD AC coil, and LC1F. It can be combined with various power contactors, including LC1D65008B7, LC1D80D7, LC1D80008FE7, LC1D128P7, LC1D65AKUE, LC1D80MW, LC1D18M7, LC1D38Q7, LC1D150V7, LC1D115S7, LC1D150B7, LC1D25U7TQ, LC1D80U5, LC1D115004FD, LC1D80AG7, LC1DT40U7, LC1D25X7, LC1D65AJD, LC1D32KUE, and LC1D80N7. This combination enables expansion of control functions in industrial systems.
Mounting and Installation
Mounting is performed laterally to the main contactor, with screw terminals front-mounted and snap-in. Dimensions are 72 mm (height), 12.5 mm (width), and 71.3 mm (depth). Installation is carried out under normal ambient conditions, with an operating temperature range of -5 to 60 °C. The maximum operating altitude is 3,000 m. The packaging unit contains a single device, with a packaging weight of 60 g.
Operational Advantages
The auxiliary switch block provides high operational reliability due to a long mechanical life of 30 million switching cycles. The undelayed switching and short non-overlapping time of 1.5 ms ensure precise and reliable switching operations. The screw terminals allow for flexible and secure connections with various cable types. Compatibility with a wide range of TeSys Deca contactors enables flexible integration into existing systems. Compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, IEC 60335-1:Clause 30.2, and IEC 60335-2-40:Annex JJ ensures the reliability and safety of the product. Certifications including CB Regulation, UL, CSA, CCC, EAC, and UKCA confirm conformity with applicable safety and quality standards.