| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Lugs-ring terminals (external diameter: 8 mm) |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 72 mm |
| Width | 12.5 mm |
| Depth | 71.3 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Range compatibility | TeSys Deca LC1D09…95 AC coil; TeSys Deca LC1D40A…80A AC Coil; TeSys Deca LC1D115/150; TeSys Deca CAD AC coil; TeSys F LC1F |
| Mounting location | Side |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.0 cm |
| Package 1 Width | 7.3 cm |
| Package 1 Length | 8.0 cm |
| Package 1 Weight | 60.0 g |
The auxiliary switch block LAD8N116 from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for power contactors and control relays. It is specifically designed for use with LC1D contactors and CAD control relays with AC coils, enabling the integration of additional switching functions into existing installations. The device features an
auxiliary switch block with a contact configuration of 1 normally open (S) and 1 normally closed (O), switching without delay. Mounting is done laterally, with the module being clip-on, ensuring quick and secure installation on existing contactors.
Applications
The auxiliary switch block is used in industrial installations where additional switching contacts are required for control or signaling tasks. It is suitable for applications in automation technology, such as in manufacturing, process engineering, or building automation. Use is restricted to LC1D contactors from the TeSys Deca series and CAD control relays with AC coils, with compatibility limited to models LC1D09 to LC1D95, LC1D40A, LC1D115/150, CAD AC coil, and LC1F.
Functions and Equipment in Detail
The block provides an
auxiliary switch block with 1NO+1NC contacts, where the normally closed contacts are
mirror certified, ensuring symmetrical switching characteristics. The contacts switch without delay, which is important for applications requiring high switching accuracy. The rated voltage is 690 V AC at frequencies from 25 to 400 Hz, with operating rated currents varying according to voltage and switching type: 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The mechanical life expectancy is 30 million switching cycles, indicating high reliability and durability.
Technology Explained Simply
The contacts are rated for an operating voltage up to 690 V AC, with insulation strength of 690 V (IEC 60947-5-1), 600 V (UL), and 600 V (CSA). The rated make current is 140 A AC and 250 A DC, demonstrating the block’s ability to safely switch loads under various conditions. The permissible short-time current is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms, highlighting stability under short-term load peaks. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, indicating sensitivity to weak signals. Insulation resistance exceeds 10 MΩ, ensuring high electrical insulation.
Compatibility and Accessories
The auxiliary switch block is exclusively intended for the specified LC1D contactors and CAD control relays with AC coils. It can be combined with various models, including LC1D096B7, LC1D40A6LE7, LC1D126F7, CAD506F7, LC1D1286P7, LC1D326L7, CAD326P7, LC1D126B7, LC1D1506BD, LC1D1156B7, LC1D1156M5, CAD326B7, LC1D40A6P7, LC1D096R7, LC1D386F7, LC1D1506B7, LC1D1506MD, LC1D1156U7, LC1D40A6U7. Mounting is done via a lateral clamp connection, enabling secure attachment to contactors.
Mounting and Installation
Mounting is done laterally on contactors by clipping, allowing for quick and tool-free installation. Connections are made via ring terminal lugs with an outer diameter of 8 mm. The required tightening torque is 1.7 Nm, and mounting can be performed using a flat screwdriver (Ø 6 mm), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2. The dimensions of the block are 72 mm (height), 12.5 mm (width), and 71.3 mm (depth). The operating temperature range is from -5 °C to 60 °C, and the storage temperature range is from -60 °C to 80 °C. The operating altitude is up to 3,000 m above sea level.
Advantages in Operation
The auxiliary switch block offers a high mechanical life of 30 million switching cycles, enabling long service life and low maintenance frequency. The instantaneous switching of contacts ensures precise control signals. Certifications according to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, as well as product certifications CB Regulation, UL, CSA, CCC, EAC, and UKCA, ensure compliance with international safety and quality standards. Conformity with RoHS/REACH (Green Premium) demonstrates the environmental compatibility of the product. The protection rating IP20 corresponds to IEC 60529 and protects against finger contact, but not against dust or water. The coating corresponds to category TH according to IEC 60068, ensuring resistance to humid environments.