| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 72 mm |
| Width | 12.5 mm |
| Depth | 71.3 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Range compatibility | TeSys Deca LC1D09…95 AC coil; TeSys Deca LC1D115/150; TeSys Deca LC1D40A…80A AC Coil; TeSys Deca CAD AC coil; TeSys F LC1F |
| Mounting location | Side |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.900 cm |
| Package 1 Width | 7.300 cm |
| Package 1 Length | 8.100 cm |
| Package 1 Weight | 60.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 60 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.124 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 960 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 79.000 kg |
The auxiliary switch block LAD8N11 from the TeSys Deca series by Schneider Electric is an instantaneous auxiliary contact module designed specifically for side mounting on power contactors of the TeSys Deca and TeSys F series. It serves to extend the switching functions of main contacts, for example for signal transmission, controlling additional components, or providing feedback on the switching state in control and switching systems. The block features a configuration of
1 normally open contact (S) and
1 normally closed contact (Ö), which switch instantaneously, i.e. without time delay. The contacts are rated for an operating voltage of
690 V AC at frequencies from 25 to 400 Hz and comply with the standards
EN/IEC 60947-5-1,
UL 60947-5-1, and
CSA C22.2 No. 60947-5-1. The rated insulation voltage is 690 V according to IEC 60947-5-1, 600 V according to UL and CSA, enabling use in industrial applications with high voltages.
Applications
This auxiliary switch block is intended for use in industrial control and switching systems, particularly in combination with power contactors of types LC1D09 to LC1D95, LC1D115/150, LC1D40A to LC1D80A, CAD AC coils, and LC1F. It is mounted on the side of the main contact and serves to extend control functions, for example for actuating auxiliary relays, signalling operating states, or providing feedback to higher-level control devices. Mounting is front-side snap-in, enabling quick and secure installation.
Functions and Features in Detail
The block is equipped with
screw terminals suitable for connecting flexible and rigid cables with cross-sections from 1 to 4 mm². The terminals support cables with or without wire end ferrules and allow connection of one or two cables per terminal. The required
tightening torque is 1.7 Nm, and mounting can be done with a flat-head screwdriver (Ø 6 mm), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2. The mechanical life is
30 million switching cycles, ensuring high reliability in industrial applications. The minimum switching voltage is
17 V, and the minimum switching current is
5 mA, enabling use even with weak signals.
Technology Explained Simply
The contacts switch instantaneously, meaning that the normally closed and normally open contacts change position immediately upon actuation of the main contact, without any time delay. The
non-overlapping time is 1.5 ms, regardless of whether the contact is actuated by control or release. This prevents brief short circuits between contacts. The
insulation resistance is greater than 10 MΩ, ensuring high electrical insulation and safety. The permissible short-time current is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms, ensuring load capacity during transient current surges. The
conventional thermal current is 10 A at 60 °C, describing the thermal load capacity in free air.
Compatibility and Accessories
The auxiliary switch block is compatible with a wide range of power contactors from the TeSys Deca and TeSys F series, including models such as LC1D09, LC1D95, LC1D115/150, LC1D40A–80A, CAD AC coils, and LC1F. It can be combined with various power contactors to increase the number of available auxiliary contacts. Suitable accessory products include, for example, power contactors LC1D40008F7, LC1D115R7, LC1D150Q7, LC1D150GD, LC1DT25JD, LC1DT25BL, LC1D32C7, LC1DT40ED, LC1D09B7, LC1DT40U7, LC1D25F7, LC1D12U7, LC1D32EHE, CAD50B7, LC1D115Q7, LC1D50AE7, CAD50P7TQ, LC1D95G7, and LC1D80FW. These can be combined with the auxiliary switch block according to application requirements.
Mounting and Installation
Mounting is done on the side of the main contact, with the block front-side snap-in. The screw terminals enable secure and durable connection of the wiring. Dimensions are
72 mm height, 12.5 mm width, and 71.3 mm depth, allowing compact integration into existing switching systems. The operating temperature range is
-5 °C to 60 °C, and the storage temperature range is
-60 °C to 80 °C. The operating altitude is up to
3,000 m above sea level. The protection rating
IP20 according to IEC 60529 protects against finger contact and larger solid objects, but is not suitable for outdoor use or in damp environments. The coating corresponds to category
TH according to IEC 60068, ensuring high resistance to environmental influences.
Operational Advantages
The auxiliary switch block offers high mechanical life, secure and reliable switching, and easy mounting. The use of screw terminals enables flexible and robust connections. Compatibility with a wide range of power contactors in the TeSys series simplifies integration into existing systems. Compliance with international standards and certifications such as CB, UL, CSA, CCC, EAC, and UKCA ensures usability in various markets. The high insulation performance and defined non-overlapping time increase the safety and reliability of the switching system.