| Additional features |
| [Irms] Rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time power | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Degree of protection | GG fuse 10 A |
| Mechanical life | 30 Mcycles |
| Min. switching current | 5 mA |
| Min. switching voltage | 17 V |
| Non-overlapping time | 1.5 ms at de-energization, no overlap between normally closed contact (NC) and normally open contact (NO); 1.5 ms at energization, no overlap between normally closed contact (NC) and normally open contact (NO) |
| Insulation resistance | > 10 MΩ |
| Connections - terminals | Ring terminal connectors (outer diameter: 8 mm) |
| Tightening moment | 1.7 Nm - with flat screwdriver Ø 6; 1.7 Nm - with Phillips screwdriver No. 2; 1.7 Nm - with screwdriver position No. 2 |
| Height | 72 mm |
| Width | 12,5 mm |
| Depth | 71,3 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product name | TeSys Deca |
| Product or component type | Auxiliary switch block |
| Compatible product family | TeSys Deca LC1D09 - 95 AC coil; TeSys Deca LC1D115/150; TeSys Deca LC1D40A - 80 A AC coil; TeSys Deca CAD AC coil; TeSys F LC1F |
| Mounting location | Side |
| Composition of pole contact | 2 Ö |
| Contact operation | Instantaneous |
| [Ue] Operational rated voltage | 690 V AC 25 - 400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] Rated insulation voltage | 690 V conforms to IEC 60947-5-1; 600 V conforms to UL; 600 V conforms to CSA |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No. 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB regulation; UL; CSA; CCC; EAC; UKCA |
| Mounting |
| Environmental properties | Normal ambient conditions |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Coating | TH corresponds to IEC 60068 |
| Ambient temperature during storage | -60…80 °C |
| Operating ambient temperature | -5…60 °C |
| Operating altitude | 3.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 3,000 cm |
| VPE 1 width | 7,400 cm |
| VPE 1 length | 8,300 cm |
| Packaging weight (Lbs) | 60,000 g |
Standard contactors 0.06 -75 kW In addition to an attractive and functional design, the TeSys D contactors offer quick and easy installation with a narrow width of 45 or 55 mm. They meet international standards. The power sizes 40 to 65 A are equipped with EverLink terminals. These are patented and ensure a reliable and permanent connection.