| Complementary |
| Mounting location | Front side |
| Mounting mode | Clip-on |
| Suppressor technology | Varistor (peak limiting) |
| [Uc] control circuit voltage | 50...129 V AC; 50...129 V DC |
| Maximum peak voltage | 2 Uc |
| Local signalling | LED |
| Quantity per set | Set of 5 |
| Height | 26 mm |
| Width | 6 mm |
| Depth | 22 mm |
| Net weight | 0.01 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | UL 60947-5-1; CSA C22.2 No 60947-5-1; EN/IEC 60947-5-1 |
| Product certifications | UL; CSA; CE; UKCA |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Device short name | LA4K |
| Product or component type | Suppressor module |
| Product compatibility | LC1K; LP1K; LP4K; CA2K; CA3K |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 0.500 cm |
| Package 1 Width | 2.600 cm |
| Package 1 Length | 3.900 cm |
| Package 1 Weight | 5.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 2.800 cm |
| Package 2 Width | 4.200 cm |
| Package 2 Length | 5.100 cm |
| Package 2 Weight | 27.000 g |
| Unit Type of Package 3 | S01 |
| Number of Units in Package 3 | 420 |
| Package 3 Height | 15.000 cm |
| Package 3 Width | 15.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 2.537 kg |
The product LA4KE1FC from Schneider Electric is a suppression module of the TeSys series, specifically designed for suppressing overvoltages in the control circuit of small contactors. It serves as an
overvoltage limiter and is mounted directly onto the front of contactors of types LC1K, LP1K, LP4K, CA2K, and CA3K. The function is based on
varistor technology, enabling amplitude limitation to reduce sudden voltage spikes and enhance the electrical reliability of the control circuit. The control circuit voltage ranges from 50 to 129 V AC or DC, with a maximum peak voltage of up to 2 times the rated voltage (2 Uc). The unit is equipped with an
LED, enabling local signaling, for example, to indicate operating status or faults.
Applications
This suppression module is used in industrial plants where electrical disturbances caused by switching operations or external influences can endanger control circuits. It is particularly suitable for applications with small contactors in the power range of 0.06 to 5.5 kW, where stable and disturbance-free control is required. The module is mounted directly onto the contactor, creating a compact and integrated solution that minimizes space requirements.
Functions and Equipment in Detail
The module is designed as an
add-on module and is attached to the front of the contactor. Dimensions are 26 mm height, 6 mm width, and 22 mm depth, enabling compact integration into existing control systems. The
protection rating IP2x according to IEC 60529 protects against contact with fingers and larger solid objects, but is not waterproof. The operating ambient temperature ranges from -25 °C to 50 °C, while storage temperature ranges from -50 °C to 80 °C. The
protection treatment TC complies with standards IEC 60068 and DIN 50016, ensuring resistance to environmental influences such as temperature changes and mechanical stress.
Technology Explained Simply
The varistor in the module reacts to voltage spikes by reducing resistance during overvoltage and dissipating energy in the form of heat. This protects the sensitive control circuits of contactors from damage caused by electrical disturbances. The LED provides visual feedback, for example, to indicate whether the module is active or if a disturbance has occurred. Power supply is provided via the control circuit of the contactor, with voltage supply ranging from 50 to 129 V AC/DC.
Compatibility and Accessories
The module is compatible with a range of contactors from the TeSys K series, including LC1K, LP1K, LP4K, CA2K, and CA3K. It can be combined with various power contactors, such as LC1K0601F7, LC1K0901F7, or LP1K09004FD, to enhance control circuit safety. Use with auxiliary contactors such as CA3KN40FD or CA2KN22FC7 is also possible, provided the control circuit voltage remains within the permissible range.
Mounting and Installation
Mounting is done by simply snapping the module onto the front of the contactor, requiring no additional tools or fastening elements. The unit is designed for easy and quick integration into existing control systems. Compliance with standards UL 60947-5-1, CSA C22.2 No. 60947-5-1, and EN/IEC 60947-5-1 ensures adherence to international safety standards.
Operational Advantages
By integrating the suppression module, the reliability of the control circuit is increased, as sudden voltage spikes caused by switching operations or external disturbances are effectively limited. The compact design and simple mounting reduce installation effort. Local signaling via the LED enables quick diagnosis of operating conditions. Certifications UL, CSA, CE, and UKCA ensure suitability for use in various markets and applications.