| Complementary |
| Irms rated making capacity | 110 A at |
| Permissible short-time rating | 80 A 1 s; 60 A 500 ms; 110 A 100 ms |
| Associated fuse rating | 10 A gG at |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1.5…4 mm²rigid; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²rigid |
| Tightening torque | 1.3 N.m - with screwdriver Philips No 2; 1.3 N.m - with screwdriver pozidriv No 2 |
| Height | 30 mm |
| Width | 38 mm |
| Depth | 35 mm |
| Net weight | 0.045 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for storage | -50…80 °C |
| Ambient air temperature for operation | -25…50 °C |
| Operating altitude | 2000 m |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys K |
| Product or component type | Auxiliary contact block |
| Device short name | LA1 |
| Range compatibility | TeSys K LC1K; TeSys K CA2K; TeSys K CA3K |
| Mounting location | Front |
| Pole contact composition | 4 NO |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL 60947-5-1; 600 V conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; JIS C8201-5-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; UL; CSA; CE; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.700 cm |
| Package 1 Width | 4.000 cm |
| Package 1 Length | 4.000 cm |
| Package 1 Weight | 40.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 5.000 cm |
| Package 2 Width | 17.000 cm |
| Package 2 Length | 17.000 cm |
| Package 2 Weight | 401.000 g |
| Unit Type of Package 3 | S02 |
| Number of Units in Package 3 | 100 |
| Package 3 Height | 15.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 4.500 kg |
The auxiliary switch block LA1KN40 from the TeSys series by Schneider Electric is an undelayed auxiliary switch module specifically designed for mounting on the front side of power contactors from the TeSys K series (LC1K, CA2K, CA3K). It serves as an additional switching contact to transmit signals in control and switching installations, for example, to indicate the switching state or to control other components. The device features four normally closed contacts (4 S) and is equipped with screw terminals that enable a secure and reliable connection to cables with a cross-section of 0.34 to 4 mm², supporting both flexible cables with wire end ferrules or without, as well as rigidly installed conductors. Mounting is front-side and snap-in, allowing for easy installation without tools.
Applications
The auxiliary switch block LA1KN40 is used in industrial control systems and switching installations where additional switching contacts are required for signal transmission. It is particularly suitable for applications in automation technology, such as in manufacturing, packaging technology, or building automation. The device is used in combination with power contactors from the TeSys K series, with signals transmitted via the 4 normally closed contacts. The operating voltage is up to 690 V AC in the range of 25 to 400 Hz, enabling use in industrial networks with high voltages.
Functions and Equipment in Detail
The auxiliary switch block is designed to be undelayed, meaning the contacts switch immediately upon actuation of the main contact, without any delay. The screw terminals allow for a secure connection to cables of various cross-sections, with a tightening torque of 1.3 Nm required, to be achieved using a Phillips screwdriver No. 2 or position No. 2. The contacts are rated for a conventional thermal current of 10 A at 50 °C, ensuring reliable performance in typical industrial environments. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, ensuring reliability even under low-load conditions.
Technology Explained Simply
The insulation resistance exceeds 10 MΩ, ensuring high electrical insulation and thus secure isolation of the contacts. The rated insulation voltage is 690 V according to IEC 60947-5-1, enabling use in high-voltage installations. The permissible short-time current is 80 A for 1 second, 60 A for 500 ms, and 110 A for 100 ms, ensuring reliability under short-term current surges. The associated fuse is specified as 10 A gG to ensure safety in case of faults. The protection rating IP20 corresponds to IEC 60529 and protects against finger contact, but not against dust or water, requiring use within enclosed enclosures.
Compatibility and Accessories
The auxiliary switch block LA1KN40 is compatible with power contactors from the TeSys K series, particularly models LC1K, CA2K, and CA3K. It can be combined with various power contactors, such as LC1K0601U7, LC1K0910B7, LC1K0610F7, or LC1K1210F7, to extend control functions. Additionally, auxiliary contactors such as CA3KN40MD3 or CA2KN22U7 are available and can also be integrated into the TeSys K series. Combining with other auxiliary switch blocks enables flexible expansion of switching functions.
Mounting and Installation
Mounting is performed on the front side of the corresponding power contactors from the TeSys K series. The snap-in connection allows for quick and tool-free installation. Dimensions are 38 mm width, 30 mm height, and 35 mm depth, enabling compact placement in enclosures. The operating temperature ranges from -25 °C to 50 °C, with a storage temperature range of -50 °C to 80 °C. The operating altitude is up to 2,000 m above sea level, enabling use in various geographical regions.
Operational Advantages
The auxiliary switch block LA1KN40 provides reliable signal transmission in industrial installations. The undelayed switching ensures precise synchronization with the main contact. The screw terminals allow for flexible and secure connections to various cable types. The high insulation resistance and specified fuse enhance operational safety. Compatibility with the TeSys K series and easy mounting simplify integration into existing installations. Certifications according to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, and JIS C8201-5-1, as well as product certifications CB, CCC, UL, CSA, CE, and UKCA, confirm compliance with international standards.