| Complementary |
| Protection type | GG fuse 10 A for non-protected contact |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 1 mA for protected contact; 5 mA for non-protected contact |
| Minimum switching voltage | 5 V for protected contact; 17 V for non-protected contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid; Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 39 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Harsh environment |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air temperature for operation | -25…70 °C |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Device short name | LA1 |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 2 NO (sealed) + 1 NO + 1 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 125 V AC for protected contact; 30 V DC for protected contact; 690 V AC for non-protected contact |
| [Ie] rated operational current | 0.1 A for protected contact |
| [Ui] rated insulation voltage | 250 V - for protected contact conforming to IEC 60947-5-1; 690 V - for non-protected contact conforming to IEC 60947-5-1; 600 V - for non-protected contact conforming to UL 60947-5-1; 600 V - for non-protected contact conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A (at 40 °C) for non-protected contact |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5 |
| Product certifications | CB; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.700 cm |
| Package 1 Width | 4.800 cm |
| Package 1 Length | 5.200 cm |
| Package 1 Weight | 64.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 80 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.463 kg |
Instantaneous auxiliary contact block for TeSys D and TeSys F contactors. It offers 2 NO contacts with dust and moisture protected contacts with a rated voltage up to 125 V AC and 30 V DC, 1 NO + 1 NC with protection up to 10 A, 690 V AC, connection via screw terminals. Easy front clip-on mounting, for high reliability and durability. It has multiple standards (IEC, UL, CSA, CCC) and Green Premium compliance (RoHs/Reach).