Further information for Schneider Electric KNA100DF410 - Canalis - flexible edgewise length - 100 A - 2D - 1 m - left or rig
Canalis busbar trunking system for KNA. It is used for the distribution of small powers. The operating voltage ranges from 230VAC to 500VAC 50/60Hz. The rated operating current is 100A at 35¿. It offers a white surface treatment according to RAL 9001. Mounting by screws on the left or right side of the trunking. The operating ambient temperature is between 0°C and 35°C without derating. Version with 1 branch possibility. It offers a radiated magnetic field of 186 pT. It offers 2 dimensions for direction change. It offers IP55 protection according to IEC 60529. IK08 is compliant with EN/IEC 62262. It is compliant with both IEC 60439-2 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).