| Communications & Management |
| Display type | LCD display |
| Information displayed | Resistance value; Capacitance value; Evolution of resistance in graph |
| User language | Spanish; German; Italian; Russian; French; Chinese; English; Portuguese |
| Local signalling | Yellow indicator light: insulation fault; Yellow flashing indicator light: communication; Green/red indicator light: product status; Green indicator light: satisfactory insulation; LCD display: transient fault |
| Signal contacts composition | 1 C/O standard or fail-safe |
| Signalling circuit voltage | 250 V - AC at 6 A; 48 V - DC at 1 A |
| Communication port protocol | Modbus RS485 |
| Fault event log | Alarm logs |
| Complementary |
| Alarm threshold setting | Alarm: 200 Ohm...200 kOhm |
| Type of measurement | History of alarms; Network insulation resistance, range: 200 Ohm...250 kOhm; Earth leakage capacitance, range: 0.1...15 µF |
| Accuracy | +/- 15 % |
| Channel alarm threshold setting | Alarm threshold: settable per feeder |
| Configurable filtering time | 5 s; 40 s; 400 s |
| Response time | 1 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 80 s 1/5th of set filtering time |
| Time delay range | 0...120 min for signalling circuit |
| Power quality analysis | Transient capture |
| Monitoring function | Detection of toroids connection automatic; Detection of toroids connection manual mode; Detection of IM400 injection current permanent |
| Self-test | Auto test at start and every 5h; Remote test; Manual |
| Overvoltage category | III 300 V; II 600 V |
| IP degree of protection | Case: IP20; Front face: IP54 |
| Material | Thermoplastic |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | Vigilohm |
| Device short name | IFL12MC |
| Product or component type | Insulation fault locator |
| Earthing system | IT; HRG |
| Application | Marine and offshore; Industry; Infrastructure; Power generation; Port, airport, railway |
| Network size | Large |
| Electrical circuit type | Power circuit; Control/command circuit |
| Network capacitance | Capacitive |
| Type of network | 1P + N; 3P; 3P + N |
| Network rated voltage | 0…480 V - AC at 45...440 Hz (device connected to phase) ; 0…830 V - AC at 45...440 Hz (device connected to neutral) ; 480…1000 V - AC at 45...440 Hz (device connected to phase with PHT1000 subassembly) ; 830…1000 V - AC at 45...440 Hz (device connected to neutral with PHT1000 subassembly) ; 0…480 V - DC; 480…1000 V - DC (device connected with PHT1000) |
| Number of channels | 12 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.7 cm |
| Package 1 Width | 18.2 cm |
| Package 1 Length | 13.5 cm |
| Package 1 Weight | 550.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 5.2 kg |
| Physical |
| Type of installation | Indoor |
| Relative humidity | 5…92 % |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Pollution degree | 2 |
| Mounting mode | Flush-mounted (panel); Clip-on (DIN rail) |
| Mounting position | Vertical; Horizontal |
| Connections - terminals | Power supply: removable screw terminal block 0.2…2.5 mm²; Output relay: removable screw terminal block 0.2…2.5 mm²; Toroids inputs: removable screw terminal block 0.2…1.5 mm²; Communication: removable screw terminal block 0.2…2.5 mm²; Voltage inputs: removable screw terminal block 0.2…2.5 mm² |
| Net weight | 0.305 kg |
| Cut-out dimensions | 92 x 104 mm |
| Height | 110 mm |
| Width | 108 mm |
| Depth | 59 mm |
| Power Requirements |
| [Us] rated supply voltage | 100...300 V (LN) AC 50/60 Hz tolerance: +/- 15 %; 100...440 V AC 50/60 Hz tolerance: +/- 15 %; 80…120 V (LN) AC 400 Hz tolerance: +/- 15 %; 100...440 V DC tolerance: +/- 15 % |
| Power consumption in VA | 26 VA |
| Power consumption in W | 10 W |
| Overcurrent protection | 1 A |
| Standards |
| Standards | IEC 60364-4-41; IEC 61010-1; IEC 60364-5-51; IEC 61557-9; IEC 61557-15; IEC 61326-2-4; UL 61010-1 |
| Product certifications | CE; DNV-GL; EAC; UL; cULus |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3 |
This device belongs to the Vigilohm range, designed for monitoring unearthed power supplies (IT systems) in accordance with installation and product standards. This insulation fault location is only possible when connected to the IM400 series, XM300 or XM200. This device is designed to monitor 12 AC, DC and ACDC feeders up to 1000V with the IFL12VA1T voltage adapter. It measures the insulation resistance and leakage capacitance per feeder. The configuration is set from the front of the device, via the HMI screen or via the communication interface. The main settings relate to the alarm thresholds, channel naming, toroid type (Vigilohm type or other compatible types) and filtering time. Per feeder, it displays an insulation resistance from 100 Ohm to 250 kilohms and a leakage capacitance from 1 to 15 microfarads. Autotest starts automatically every 5 hours and when required. If the insulation resistance falls below the set threshold, an alarm is triggered via the IFL output relay, HMI and communication interface. Once no more faults are detected, the alarm is cleared and the alarm relay returns to normal. The unit can be powered from a 110VAC to 440VAC source or a 110VDC to 440VDC source, all with a tolerance of plus or minus 15%.