| Communications & Management |
| Display type | Without display |
| Local signalling | Yellow indicator light: insulation fault; Green/red indicator light: product status; Green indicator light: satisfactory insulation; Yellow flashing indicator light: transient fault; Green indicator light: configured threshold LED; Green indicator light: configured filtering LED; Yellow steady 1 LED per channel: insulation fault; Yellow flashing 1 LED per channel: transient fault/toroid disconnected |
| Signal contacts composition | 1 C/O standard |
| Signalling circuit voltage | 250 V - AC at 6 A; 48 V - DC at 1 A |
| Communication port protocol | - |
| Complementary |
| Alarm threshold setting | Alarm: high, medium, low |
| Type of measurement | Network insulation resistance, range: 200 Ohm...250 kOhm |
| Channel alarm threshold setting | Alarm threshold: common to all feeders |
| Configurable filtering time | 5 s; 40 s |
| Response time | 1 s 1/5th of set filtering time; 8 s 1/5th of set filtering time |
| Power quality analysis | Transient capture |
| Monitoring function | Detection of toroids connection automatic; Detection of toroids connection manual mode; Detection of IM400 injection current permanent |
| Self-test | Manual; Auto test at start and every 5h |
| Overvoltage category | III 300 V; II 600 V |
| IP degree of protection | Case: IP20; Front face: IP54 |
| Material | Thermoplastic |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main |
| Range | Vigilohm |
| Device short name | IFL12 |
| Product or component type | Insulation fault locator |
| Earthing system | IT; HRG |
| Application | Marine and offshore; Industry; Infrastructure; Power generation; Port, airport, railway |
| Network size | Medium |
| Electrical circuit type | Power circuit |
| Network capacitance | Lightly capacitive |
| Type of network | 1P + N; 3P; 3P + N |
| Network rated voltage | 0…1000 V - AC at 45...65 Hz; 0…1000 V - DC |
| Number of channels | 12 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.500 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 526.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.690 kg |
| Physical |
| Type of installation | Indoor |
| Relative humidity | 5…92 % |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Pollution degree | 2 |
| Mounting mode | Flush-mounted (panel); Clip-on (DIN rail) |
| Mounting position | Horizontal; Vertical |
| Connections - terminals | Power supply: removable screw terminal block 0.2…2.5 mm²; Output relay: removable screw terminal block 0.2…2.5 mm²; Toroids inputs: removable screw terminal block 0.2…1.5 mm² |
| Net weight | 0.28 kg |
| Cut-out dimensions | 92 x 104 mm |
| Height | 110 mm |
| Width | 108 mm |
| Depth | 59 mm |
| Power Requirements |
| [Us] rated supply voltage | 100...300 V (LN) AC 50/60 Hz tolerance: +/- 15 %; 100...440 V AC 50/60 Hz tolerance: +/- 15 %; 80…120 V (LN) AC 400 Hz tolerance: +/- 15 %; 100...440 V DC tolerance: +/- 15 % |
| Power consumption in VA | 20 VA |
| Power consumption in W | 6 W |
| Overcurrent protection | 1 A |
| Standards |
| Standards | IEC 60364-4-41; IEC 61010-1; IEC 60364-5-51; IEC 61557-9; IEC 61557-15; IEC 61326-2-4; UL 61010-1 |
| Product certifications | DNV-GL; CE; EAC; UL; cULus |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3 |
This device belongs to the Vigilohm range designed for monitoring ungrounded power supplies (IT systems) in accordance with installation and product standards. This insulation fault location is only possible when connected to IM400 series, XM300 or XM200. This device is designed to monitor 12 AC, DC and ACDC feeders up to toroidal voltage of 1000 V. The configuration is set from the front of the device through the HMI screen. The settings refer to the alarm thresholds. It indicates which feeder has an insulation fault. Autotest starts automatically every 5 hours and when required. If the insulation resistance drops below the set threshold, an alarm is triggered via the IFL output relay and the HMI. Once no more fault is detected, the alarm is cleared and the alarm relay returns to normal state. The unit can be powered from a 110VAC to 440VAC source or a 110VDC to 440VDC source, all with a tolerance of plus or minus 15%.