| Communications & Management |
| Display type | LCD display |
| Information displayed | Resistance value; Capacitance value; Evolution of resistance in graph |
| User language | Portuguese; Italian; French; German; English; Chinese; Russian; Spanish |
| Local signalling | Green indicator light: satisfactory insulation resistance; White indicator light: below prevention threshold; Red indicator light: wiring or internal fault; Yellow indicator light: insulation fault; Yellow flashing indicator light: communication |
| Signal contacts composition | 2 C/O standard or fail-safe |
| Signalling circuit voltage | 250 V - AC at 3 A; 48 V - DC at 1 A |
| Communication port protocol | Modbus RS485 |
| Communication of data | HMI: test reports; Dry contact: test reports |
| Fault event log | Alarm logs; Time stamping; 30 events |
| Complementary |
| Alarm threshold setting | Pre-alarm: 1 kOhm...1 MOhm; Alarm: 40 Ohm...500 kOhm |
| Type of measurement | Network insulation resistance, range: 10 Ohm...10 MOhm, accuracy: +/- 1 %; Earth leakage capacitance, range: 0.01...5500 µF, accuracy: +/- 5 % |
| Configurable filtering time | 4 s; 40 s; 400 s |
| Response time | 0.8 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 80 s 1/5th of set filtering time |
| Time delay range | 0...120 min for signalling circuit; 0...120 min for alarm |
| Power quality analysis | Transient capture |
| Input type | Contact for injection inhibition Dry contact; Contact for injection inhibition Modbus |
| Operating mode | Control; Power; Marine; Photovoltaic; Railway |
| Self-test | Manual; Auto test at start and every 5h |
| Overvoltage category | III 300 V; II 600 V |
| IP degree of protection | Case: IP20; Front face: IP54 |
| Material | Thermoplastic |
| Harsh environment | Coated |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | Vigilohm |
| Device short name | IM400C |
| Product or component type | Insulation monitoring device |
| Type of IMD | AC/DC IMD |
| Earthing system | IT; HRG |
| Application | Marine and offshore; Industry; Infrastructure; Power generation; Port, airport, railway; Photovoltaic |
| Network size | Large |
| Electrical circuit type | Power circuit; Control circuit |
| Network capacitance | Highly capacitive |
| Type of network | 1P + N; 3P; 3P + N |
| Network rated voltage | 0…480 V - AC at 45...440 Hz (device connected to phase) ; 0…830 V - AC at 45...440 Hz (device connected to neutral) ; 0…480 V - DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.5 cm |
| Package 1 Width | 18.0 cm |
| Package 1 Length | 21.5 cm |
| Package 1 Weight | 953.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 4.442 kg |
| Physical |
| Type of installation | Indoor; Enclosed outdoor |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Pollution degree | 2 |
| Mounting mode | Flush-mounted (panel) |
| Mounting position | Horizontal |
| Connections - terminals | Removable screw terminal block 0.2…2.5 mm² |
| Net weight | 0.66 kg |
| Cut-out dimensions | 112 x 148 mm |
| Height | 123 mm |
| Width | 159 mm |
| Depth | 90 mm |
| Power Requirements |
| [Us] rated supply voltage | 100...440 V AC 50/60/400 Hz tolerance: +/- 15 %; 100...440 V DC tolerance: +/- 15 % |
| Power consumption in VA | 25 VA |
| Power consumption in W | 10 W |
| Overcurrent protection | 1 A |
| Standards |
| Standards | IEC 60364-4-41; IEC 61010-1; IEC 61557-8; UL 61010-1; IEC 61326-2-4; EN/IEC 61508 level SIL2; UL 1998 |
| Product certifications | RMRS; DNV; CSA; ABS; UL; cULus; EAC; CE; EU-RO MR TA; RCM |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3 |
| Supported Hardware |
| Product compatibility | Automatic fault locator |
Dieses Gerät gehört zur Vigilohm Reihe, die für die Überwachung von ungeerdeten Energieversorgungen (IT-Systeme) gemäß den Installations- und Produktnormen entwickelt wurde. Gemäß den Normen wird empfohlen, Ihre Systeme mit Isolationsüberwachungsgeräten (IMD) auszurüsten. Dieses Gerät ist für die Überwachung von großen und gestörten AC-, DC- und ACDC-Systemen bestimmt, einschließlich großer Photovoltaik-Anwendungen. Es misst den Netzisolationswiderstand durch Einspeisung eines niederfrequenten Wechselstroms zwischen Netz und Erde. Die Konfiguration hängt von der Installation ab. Die Einstellungen erfolgen auf der Vorderseite des Geräts über den HMI-Bildschirm. Die Einstellungen beziehen sich auf den Netzwerktyp, die Alarm- und Voralarmschwellen, die Alarmverzögerung von 0 bis 7200 Sekunden und andere sind verfügbar. Es überwacht Netze bis zu 830VAC bei Anschluss an den Nullleiter, 480V bei Anschluss an die Leitung und 480VDC, mit bis zu 500Microfarad, bis zu 5500Microfarad im PV-Modus mit Spannungsadapter. Der Schwarz-Weiß-Bildschirm kann den Isolationswiderstand von 10 Ohm bis 10 Megaohm, die Kapazität und temporäre Fehler anzeigen. Autotest startet automatisch alle 5 Stunden und bei Bedarf. Fällt der Isolationswiderstand des Systems unter den eingestellten Schwellenwert, d.h. liegt ein Erdschluss vor, wird über das IMD-Ausgangsrelais ein Alarm ausgelöst. Sobald kein Fehler mehr erkannt wird, wird der Alarm gelöscht und das Alarmrelais kehrt in den Normalzustand zurück. Das Gerät kann von einer 110VAC bis 440VAC Quelle oder einer 110VDC bis 440VDC Quelle versorgt werden, alle mit einer Toleranz von plus oder minus 15%. Dieses Produkt wird flächenbündig installiert, z. B. in einer Schranktür, und ist konform beschichtet. Frontseitige Schutzart ist IP5, rückseitige Schutzart IP20 und Überspannung 300V Kategorie III. Das Überwachungsgerät ist mit einer RS485-Kommunikationsschnittstelle mit Modbus-Protokoll ausgestattet.