| Communications & Management |
| Display type | LCD display |
| Information displayed | Resistance value; Capacitance value; Evolution of resistance in graph |
| User language | Italian; French; German; Chinese; Portuguese; Russian; Spanish; English |
| Local signalling | Green indicator light: satisfactory insulation resistance; White indicator light: below prevention threshold; Red indicator light: wiring or internal fault; Yellow indicator light: insulation fault; Yellow flashing indicator light: communication |
| Signal contacts composition | 2 C/O standard or fail-safe |
| Signalling circuit voltage | 250 V - AC at 3 A; 48 V - DC at 1 A |
| Communication port protocol | Modbus RS485 |
| Communication of data | HMI: test reports; Dry contact: test reports |
| Fault event log | Alarm logs; Time stamping; 30 events |
| Complementary |
| Alarm threshold setting | Pre-alarm: 1 kOhm...1 MOhm; Alarm: 40 Ohm...500 kOhm |
| Type of measurement | Network insulation resistance, range: 10 Ohm...10 MOhm, accuracy: +/- 1 %; Earth leakage capacitance, range: 0.01...500 µF, accuracy: +/- 5 % |
| Configurable filtering time | 4 s; 40 s; 400 s |
| Response time | 0.8 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 80 s 1/5th of set filtering time |
| Time delay range | 0...120 min for signalling circuit; 0...120 min for alarm |
| Power quality analysis | Transient capture |
| Input type | Contact for injection inhibition Dry contact; Contact for injection inhibition Modbus |
| Operating mode | Control; Power |
| Self-test | Manual; Auto test at start and every 5h |
| Overvoltage category | III 300 V; II 600 V |
| IP degree of protection | Case: IP20; Front face: IP54 |
| Material | Thermoplastic |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | Vigilohm |
| Device short name | IM400 |
| Product or component type | Insulation monitoring device |
| Type of IMD | AC/DC IMD |
| Earthing system | IT; HRG |
| Application | Marine and offshore; Industry; Infrastructure; Power generation; Port, airport, railway |
| Network size | Large |
| Electrical circuit type | Power circuit; Control circuit |
| Network capacitance | Very capacitive |
| Type of network | 1P + N; 3P; 3P + N |
| Network rated voltage | 0…480 V - AC at 45...440 Hz (device connected to phase) ; 0…830 V - AC at 45...440 Hz (device connected to neutral) ; 0…480 V - DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.000 cm |
| Package 1 Width | 17.500 cm |
| Package 1 Length | 21.200 cm |
| Package 1 Weight | 956.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.530 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 32 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 43.500 kg |
| Physical |
| Type of installation | Indoor |
| Relative humidity | 0…92 % |
| Ambient air temperature for operation | -25…55 °C |
| Ambient air temperature for storage | -40…70 °C |
| Pollution degree | 2 |
| Mounting mode | Flush-mounted (panel) |
| Mounting position | Horizontal |
| Connections - terminals | Removable screw terminal block 0.2…2.5 mm² |
| Net weight | 0.645 kg |
| Cut-out dimensions | 112 x 148 mm |
| Height | 123 mm |
| Width | 159 mm |
| Depth | 90 mm |
| Power Requirements |
| [Us] rated supply voltage | 100...440 V AC 50/60/400 Hz tolerance: +/- 15 %; 100...440 V DC tolerance: +/- 15 % |
| Power consumption in VA | 25 VA |
| Power consumption in W | 10 W |
| Overcurrent protection | 1 A |
| Standards |
| Standards | IEC 60364-4-41; IEC 61010-1; IEC 61557-8; UL 61010-1; IEC 61326-2-4; EN/IEC 61508 level SIL2 |
| Product certifications | DNV; RMRS; CE; ABS; EAC; CSA; cULus; UL; EU-RO MR TA; RCM |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3 |
| Supported Hardware |
| Product compatibility | Automatic fault locator |
This device belongs to the Vigilohm range designed for the monitoring of unearthed power supplies (IT systems) in accordance with installation and product standards. According to the standards, it is recommended to equip your systems with insulation monitoring devices (IMD). This device is intended for the monitoring of large and disturbed AC, DC and ACDC systems. It measures the network insulation resistance by injecting a low frequency alternating current between the network and earth. The configuration is set depending on the installation. The settings are made on the front of the device, from the HMI screen or from the communication port. The settings refer to the network type, the alarm and pre-alarm thresholds, the alarm delay from 0 to 7200 seconds and others are available. It monitors networks up to 830VAC when connected to the neutral, 480V when connected to the line and 480VDC, with up to 500microfarad. The black and white screen can display insulation resistance from 10 ohms to 10 megohms, capacitance and temporary faults. Autotest starts automatically every 5 hours and when required. If the insulation resistance of the system falls below the set threshold, i.e. there is an earth fault, an alarm is triggered via the IMD output relay. Once no more faults are detected, the alarm is cleared and the alarm relay returns to normal. The device can be powered from a 110VAC to 440VAC source or a 110VDC to 440VDC source, all with a tolerance of plus or minus 15%. This product is flush mounted, e.g. in a control cabinet door. Front protection class is IP5, rear protection class IP20 and overvoltage 300V category III. The monitoring device is equipped with an RS485 communication interface with Modbus protocol.