| Communications & Management |
| Display type | LCD display |
| Information displayed | Resistance value; IT transformer alarms; Evolution of resistance in graph |
| User language | Russian; Spanish; French; Chinese; German; Portuguese; English; Italian |
| Local signalling | Green indicator light: satisfactory insulation resistance; Orange audible and visible alarms: below fault threshold |
| Signal contacts composition | 2 C/O standard or fail-safe |
| Signalling circuit voltage | 12...48 V - DC at 50 mA |
| Communication port protocol | Modbus RS485 |
| Communication of data | HMI: test reports; Dry contact: test reports |
| Fault event log | Alarm logs |
| Complementary |
| Alarm threshold setting | Alarm: 50...500 kOhm |
| Type of measurement | Network insulation resistance, range: 1 kOhm...10 MOhm, accuracy: +/- 5 %; History of alarms |
| Configurable filtering time | 1 s |
| Response time | 0.8 s 1/5th of set filtering time; 8 s 1/5th of set filtering time; 32 s 1/5th of set filtering time |
| Alarm function | IT transformer overheat; IT transformer overload |
| Self-test | Manual; Auto test |
| Relative impedance | 141 kOhm at 2.5 Hz |
| IP degree of protection | Front face: IP52; Rear: IP20 |
| Material | Thermoplastic |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | Vigilohm |
| Device short name | IM20-H |
| Product or component type | Insulation monitoring device |
| Type of IMD | AC IMD |
| Earthing system | IT |
| Application | Group II medical premise; Healthcare |
| Electrical circuit type | Control circuit |
| Network capacitance | Lightly capacitive |
| Type of network | 1P + N |
| Network rated voltage | 0…230 V - AC at 50/60 Hz (device connected to neutral) ; 0…230 V - DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.500 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 16.500 cm |
| Package 1 Weight | 457.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.347 kg |
| Physical |
| Type of installation | Indoor |
| Relative humidity | 0…92 % |
| Ambient air temperature for operation | -25…55 °C |
| Ambient air temperature for storage | -40…70 °C |
| Pollution degree | 2 |
| Mounting mode | Clip-on (DIN rail); Flush-mounted (panel) |
| Connections - terminals | Removable screw terminal block 0.2…2.5 mm² |
| Net weight | 0.25 kg |
| Cut-out dimensions | 92.4 x 92.4 mm |
| Height | 110 mm |
| Width | 96 mm |
| Depth | 59 mm |
| Power Requirements |
| [Us] rated supply voltage | 110...230 V AC 50/60 Hz tolerance: +/- 15 %; 125...250 V DC tolerance: +/- 15 % |
| Power consumption in VA | 12 VA |
| Overcurrent protection | 1 A |
| Standards |
| Standards | IEC 61010-1; IEC 61557-8; IEC 60364-7-710; IEC 61326-2-4; UL 61010-1 |
| Product certifications | DNV; EAC; BV; CE; EU-RO MR TA |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3 |
| Supported Hardware |
| Product compatibility | Automatic fault locator |
Dieses Gerät gehört zur Vigilohm Reihe, die für die Überwachung von ungeerdeten Energieversorgungen (IT-Systeme) gemäß den Installations- und Produktnormen entwickelt wurde. Gemäß den IEC Normen ist es vorgeschrieben, IT-Medizinräume mit Isolationsüberwachungsgeräten (IMD) auszustatten. Dieses Gerät ist für die Überwachung von AC-, DC- und ACDC-Systemen für medizinische IT-Systeme bestimmt. Es misst den Netzisolationswiderstand durch Einspeisung eines niederfrequenten Wechselstroms zwischen Netz und Erde. Die Konfiguration wird gemäß den medizinischen Standards von der Vorderseite des Geräts aus über den HMI-Bildschirm vorgenommen. Die Einstellungen beziehen sich auf Isolationsalarmschwellen von 50 bis 500 Kiloohm sowie auf Überhitzungs- und Überlastalarme für Transformatoren. Es überwacht Netze bis zu 230VAC, 230VDC, in der medizinischen IT-Architektur, sowie den medizinischen IT-Transformator. Der Schwarz-Weiß-Bildschirm kann den Isolationswiderstand von 100 Ohm bis 10 Megohm anzeigen. Autotest startet automatisch alle 5 Stunden und bei Bedarf. Fällt der Isolationswiderstand des Systems unter den eingestellten Schwellenwert, d.h. es liegt ein Erdschluss vor, wird innerhalb von 4 Sekunden über das IMD-Ausgangsrelais ein Alarm ausgelöst. Sobald kein Fehler mehr erkannt wird, wird der Alarm gelöscht und das Alarmrelais kehrt in den Normalzustand zurück. Das Gerät kann von einer 110VAC bis 230VAC Quelle oder einer 125VDC bis 250VDC versorgt werden, alle mit einer Toleranz von plus oder minus 15%. Dieses Produkt kann auf einer DIN-Schiene oder bündig montiert werden. Frontseitige Schutzart ist IP52, rückseitig IP20 und Überspannungskategorie III. Das Überwachungsgerät ist mit einer RS485-Kommunikationsschnittstelle mit Modbus-Protokoll ausgestattet.