| Additional features |
| [In] Rated current | 110 A |
| Number of Poles | 3P |
| Description of protected poles | 3t |
| Control type | Toggle switch |
| Breaking capacity | L |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz compliant with IEC 60947-3 |
| Network frequency | 50/60 Hz |
| [Ics] Rated operational breaking capacity | 125 kA at 220/240 V AC 50/60 Hz complies with IEC 60947-2; 100 kA at 380/440/415 V AC 50/60 Hz complies with IEC 60947-2; 50 kA at 500/525 V AC 50/60 Hz complies with IEC 60947-2; 20 kA at 250 V DC complies with IEC 60947-2; 20 kA at 500 V DC complies with IEC 60947-2 |
| [Uimp] Rated impulse voltage withstand | 8 kV corresponds to IEC 60947-2 |
| Tripping unit technology | Thermal-magnetic |
| Magnetic trip current | 1700 A |
| Magnetic holding current | 900 A |
| Nominal current | 80 % |
| [Ui] Rated insulation voltage | 750 V corresponds to IEC 60947-2 |
| Suitability for insulation | Yes, complies with IEC 60947-2 |
| Application category | Category A |
| AWG gauge | AWG 14 - AWG 3/0 aluminium/copper terminal |
| Local signalling | Switched off (OFF): 1 trip indicator (green) |
| Mounting mode | Device holder (peg) |
| Mounting bracket | Tappet |
| Electrical connection | Cable lugs, line; Cable lugs, load |
| Terminal designation | AL150HD |
| Tightening moment | 5 Nm for 2.5…6 mm² (AWG 14 - AWG 10); 14 Nm for 10…95 mm² (8 AWG...3/0 AWG) |
| Number of slots | 2 auxiliary switch sockets OF (pluggable); 1 alarm switch socket SD (pluggable); 1 overcurrent trip switch socket SDE (pluggable); 1 voltage release socket MN or MX (pluggable) |
| Power wire stripping length | 16 mm |
| Colour | Black |
| Height | 163 mm |
| Width | 104 mm |
| Depth | 86 mm |
| Product weight | 2,2 kg |
| Quantity per set | 1 |
| Communication interface | Modbus; Ethernet |
| Application of power switches | HACR rating |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | PowerPact |
| Product name | PowerPact H |
| Product or component type | Power-cut-out switch |
| Device application | Distribution |
| Mounting |
| Conformity marking | CE |
| Standards | UL; CSA; NEMA; NOM-003-SCFI-2000; IEC 60947-2 |
| Product certifications | UL; CSA; NOM |
| Degree of protection (IP) | Front cover: IP40 in accordance with IEC 60529 |
| Pollution degree | 3 corresponds to IEC 60947-1 |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -50…85 °C |
| Operating altitude | < 2,000 m without power reduction; 5,000 m with power reduction |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 14,5 cm |
| VPE 1 width | 19,1 cm |
| VPE 1 length | 22,1 cm |
| Packaging weight (Lbs) | 1,86 kg |
The PowerPacT H, J and L frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. H and J frame circuit breakers are available with either thermal-magnetic or electronic Micrologic releases. The new generation of PowerPacT with Micrologic circuit breakers sets the standard for direct access to energy management. Integrated metering improves their protection capabilities. For the first time, Schneider Electric users can monitor currents from 15 to 3000A, offering new performance in a remarkably compact device. This PowerPacT H circuit breaker has a rated current of 110A and is a 3P breaker. This breaker has a breaking capacity of 50kA@600V AC and features a thermal-magnetic release. This circuit breaker complies with UL, CE, IEC and CSA standards. The thermal current of this breaker has a magnetic trip current of 1700A. The dimensions of this circuit breaker are 104.6mm x 162.6mm x 110.7mm (WxHxD) and it is designed for an ambient temperature of 40°C. This product comes with an 18-month warranty.