| Additional features |
| Pole description | 3P |
| Type of network | AC |
| Application category | AC-3 |
| Network frequency | 50/60 Hz corresponds to IEC 60947-2 |
| Mounting mode | By clips; By screws |
| Mounting bracket | Rail |
| Mounting position | Any position |
| Motor power (kW) | 2.2 kW at 230 V AC 50/60 Hz; 4 kW at 400 V AC 50/60 Hz; 4 kW at 440 V AC 50/60 Hz; 5.5 kW at 500 V AC 50/60 Hz; 7.5 kW at 690 V AC 50/60 Hz |
| Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz complies with IEC 60947-2; Icu: >= 100 kA at 400/415 V AC 50/60 Hz complies with IEC 60947-2; Icu: 2 kA at 690 V AC 50/60 Hz complies with IEC 60947-2; Icu: 10 kA at 440 V AC 50/60 Hz complies with IEC 60947-2; Icu: 8 kA at 500 V AC 50/60 Hz complies with IEC 60947-2 |
| [Ics] Rated operational short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforms to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforms to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforms to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforms to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforms to IEC 60947-2 |
| Control type | Push button |
| Adjustable range for thermal protection | 6…10 A |
| Magnetic trip current | 138 A |
| [Ue] Operational rated voltage | 690 V AC 50/60 Hz complies with IEC 60947-2 |
| [Ui] Rated insulation voltage | 690 V AC 50/60 Hz complies with IEC 60947-2 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947-2 |
| Power loss | 2.5 W (per pole) |
| Mechanical life | 100000 cycles |
| Electrical lifetime | 100000 cycles for AC-3 |
| Max. operating rate | 25 cyc/h |
| Connections - terminals | Screw terminals 2 1…6 mm² - cable grip: rigid; screw terminals 2 1.5…6 mm² - cable grip: flexible without cable end; screw terminals 2 1…4 mm² - cable grip: flexible with cable end |
| Height | 89 mm |
| Width | 44,5 mm |
| Depth | 78 mm |
| Product weight | 0,26 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Easy TeSys |
| Product or component type | Power-cut-out switch |
| Device short name | GZ1E |
| Device application | Motor |
| Trigger technology | Thermal-magnetic |
| Suitability for insulation | Yes complies with IEC 60947-1 Annex 7.1.6 |
| Colour | Grey (RAL 7011) |
| Mounting |
| Standards | EN/IEC 60947-1; EN/IEC 60947-2; EN/IEC 60947-4-1; GB/T 14048.1; GB/T 14048.2; GB/T 14048.4; EN/IEC 60335-1:Clause 30.2; EN/IEC 60335-2-40:Annex JJ |
| Product certifications | CB regulation; CCC; CE; EAC |
| Coating | TH |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Operating ambient temperature | -20…60 °C |
| Ambient temperature during storage | -40…80 °C |
| Fire-resistance | 960 °C corresponds to IEC 60695-2-1 |
| Operating altitude | 2.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 4,800 cm |
| VPE 1 width | 8,400 cm |
| VPE 1 length | 9,000 cm |
| Packaging weight (Lbs) | 256,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 24 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 6,554 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 384 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 112,615 kg |