| Complementary |
| Range compatibility | TeSys GV2ME; TeSys Deca |
| Control circuit voltage limits | 0.85...1.1 Un |
| [Ui] rated insulation voltage | 690 V AC conforming to IEC 60947-1; 600 V AC conforming to UL 60947-4-1; 600 V AC conforming to CSA C22.2 No 60947-4-1 |
| Threshold tripping voltage | 0.7...0.35 Un |
| Inrush power in VA | 12 VA AC |
| Inrush power in W | 8 W |
| Hold-in power consumption in VA | 3.5 VA AC |
| Hold-in power consumption in W | 1.1 W |
| Operating time | 10...15 ms conforming to IEC 60947-1 |
| On-load factor | 100 % |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²solid; Screw clamp terminals 2 cable(s) 1…2.5 mm²solid; Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end |
| Tightening torque | < 1.4 N.m on screw clamp terminals |
| Mechanical durability | 30000 cycles |
| Quantity per set | Set of 10 |
| Height | 89 mm |
| Width | 18 mm |
| Depth | 66 mm |
| Net weight | 0.105 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Product or component type | Safety undervoltage trip |
| Device short name | GVAX |
| [Uc] control circuit voltage | 380...400 V AC 50 Hz; 440 V AC 60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.800 cm |
| Package 1 Width | 8.500 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 120.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 42 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.424 kg |
The
GVAX385 is a
safety undervoltage release from the
TeSys Deca series by
Schneider Electric, specifically developed for integration into
motor protection circuit breakers of the
TeSys GV2ME series. It protects electrical drives against unwanted operating conditions during voltage dips or failures. When the control circuit voltage falls below the predefined threshold (0.7 to 0.35 Un), the device trips and disconnects the motor from the power supply to prevent damage to the system or drive. Tripping occurs within 10 to 15 ms, in accordance with IEC 60947-1, ensuring a rapid response to voltage disturbances.
Applications
This undervoltage release is designed for industrial applications where reliable and safe motor operation is required. It is used in control systems for start-stop motors, particularly in installations that depend on stable voltage supply, such as in manufacturing, packaging technology, or conveyor system control. Compatibility with the
TeSys GV2ME series allows for easy integration into existing control panels.
Functions and Features in Detail
The device is rated for a control circuit voltage of
380 to 400 V AC at 50 Hz and
440 V AC at 60 Hz. The operating voltage must remain within the range of 0.85 to 1.1 Un to ensure safe operation. The
threshold tripping voltage is between 0.7 and 0.35 Un, enabling precise response to voltage dips. The
pickup power is 12 VA (8 W) and the
holding power consumption is 3.5 VA (1.1 W), ensuring efficient power supply in the control circuit. The mechanical life is 30,000 cycles, indicating high reliability and durability.
Technology Explained Simply
The
undervoltage release functions as an electrical safety device that monitors the voltage in the control circuit. When the voltage drops below the preset threshold, the tripping mechanism is activated and the motor is disconnected from the power supply. The rated insulation voltage is
690 V AC in accordance with IEC 60947-1, ensuring high electrical safety even in demanding environments. The terminals are
screw terminals, allowing connection of rigid cables with cross-sections of 1 to 2.5 mm² and flexible cables of 0.75 to 2.5 mm² (without cable end) or 0.75 to 1.5 mm² (with cable end). The tightening torque is less than 1.4 Nm, enabling secure and easy installation.
Compatibility and Accessories
The GVAX385 is specifically designed for use with
motor protection circuit breakers from the TeSys GV2ME series. Compatible models include, for example, the
GV2ME03,
GV2ME32,
GV2ME10, and other models within the GV2ME range, available in various current ratings and configurations. Combining it with these circuit breakers allows for flexible and modular adaptation to different drive requirements.
Mounting and Installation
Mounting is done via the integrated screw terminals, designed for various cable types and cross-sections. The device dimensions are 89 mm (height), 18 mm (width), and 66 mm (depth), allowing compact placement in enclosures. The housing color is dark grey, which blends well visually in industrial environments. Installation is typically performed in conjunction with a motor protection circuit breaker, with electrical connections made according to technical specifications.
Operational Advantages
The use of the GVAX385 ensures increased safety and reliability in electrical drive systems. The fast tripping time of 10 to 15 ms protects motors and systems from damage due to uncontrolled operation during voltage dips. The high mechanical life of 30,000 cycles and compact design simplify maintenance and replacement. Compatibility with the TeSys GV2ME family enables modular expansion and adaptation to different requirements.