| Complementary |
| Range compatibility | TeSys GV2ME; TeSys Deca |
| Control circuit voltage limits | 0.85...1.1 Un |
| [Ui] rated insulation voltage | 690 V AC conforming to IEC 60947-1; 600 V AC conforming to UL 60947-4-1; 600 V AC conforming to CSA C22.2 No 60947-4-1 |
| Threshold tripping voltage | 0.7...0.35 Un |
| Inrush power in VA | 12 VA AC |
| Inrush power in W | 8 W |
| Hold-in power consumption in VA | 3.5 VA AC |
| Hold-in power consumption in W | 1.1 W |
| Operating time | 10...15 ms conforming to IEC 60947-1 |
| On-load factor | 100 % |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²solid; Screw clamp terminals 2 cable(s) 1…2.5 mm²solid; Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end |
| Tightening torque | < 1.4 N.m on screw clamp terminals |
| Mechanical durability | 30000 cycles |
| Quantity per set | Set of 10 |
| Height | 89 mm |
| Width | 18 mm |
| Depth | 66 mm |
| Net weight | 0.105 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Product or component type | Safety undervoltage trip |
| Device short name | GVAX |
| [Uc] control circuit voltage | 220...240 V AC 50 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.800 cm |
| Package 1 Width | 8.500 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 121.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 2.130 kg |
The GVAX225 from Schneider Electric is a safety undervoltage release from the TeSys Deca series, specifically designed for integration into motor protection circuit breakers of the TeSys GV2ME series. The device protects electrical drives against unwanted operational restrictions caused by voltage dips or interruptions in the control circuit. It ensures that the connected motor is only switched on when the control circuit voltage is within the specified limits, and automatically switches it off in case of undervoltage to prevent damage.
Applications
The undervoltage release is intended for industrial applications in motor control, particularly in systems with start motors and stop motors. It is used in installations where safe and reliable operation under variable network conditions is required, for example in manufacturing plants, conveyor systems, or pump installations. Integration is carried out in existing motor protection circuit breakers from the TeSys GV2ME family, enabling modular expansion of protection functions.
Functions and Equipment in Detail
The GVAX225 operates with a control circuit voltage of 220 to 240 V AC at 50 Hz. The operating voltage must be within the range of 0.85 to 1.1 times the rated voltage to keep the release in operation. If the voltage drops below 0.7 times the rated voltage, the release is activated and switches off the motor. The release function occurs within 10 to 15 ms, meeting the requirements of standard IEC 60947-1. The pickup power is 12 VA (8 W) and the holding power consumption is 3.5 VA (1.1 W), ensuring efficient energy use. The mechanical life is 30,000 cycles, indicating high operational reliability and durability.
Technology Explained Simply
The release uses an electromagnetic actuation that closes the contact when sufficient voltage is present and opens the contact during undervoltage. The threshold release voltage of 0.7 to 0.35 times the rated voltage ensures that the motor is switched off during critical voltage dips to prevent damage to the installation. The rated insulation voltage is 690 V AC according to IEC 60947-1, enabling use in industrial environments with high voltage loads. The terminals are screw terminals and support various cable types: rigid (1–2.5 mm²), flexible without cable end (0.75–2.5 mm²), and flexible with cable end (0.75–1.5 mm²). The pickup torque is less than 1.4 Nm, ensuring secure and easy installation.
Compatibility and Accessories
The GVAX225 is specifically developed for use with motor protection circuit breakers from the TeSys GV2ME series. Compatible models include, for example, GV2ME10, GV2ME32, GV2ME03, GV2ME20, GV2ME07, GV2ME16, GV2ME22, GV2ME06, GV2ME05, GV2ME08, GV2ME01, GV2ME14, GV2ME04, GV2ME21, and GV2ME02. Combining it with these circuit breakers extends their functionality with undervoltage protection. The devices are finished in Dark Grey and have dimensions of 89 mm (height), 18 mm (width), and 66 mm (depth). The product weight is 0.105 kg.
Mounting and Installation
Mounting is done by direct installation into the motor protection circuit breaker of the TeSys GV2ME series. The screw terminals allow for secure connections with the specified cable cross-sections. Installation requires no additional tools or components, as the connection is made directly via the terminals. The maximum number of devices per set is 10 pieces, with packaging units PCE (1 piece) and S01 (16 pieces) available.
Advantages in Operation
Using the GVAX225 increases the operational safety of electrical drives by preventing unwanted motor operation during voltage dips. The fast response time of 10 to 15 ms ensures reliable protection. The high mechanical life of 30,000 cycles and the compact design enable long-lasting and space-saving integration into existing installations. Compatibility with the TeSys GV2ME family offers flexible expansion options for existing control systems.