| Complementary |
| Range compatibility | TeSys GV2ME; TeSys GV2LE; TeSys GV2L; TeSys GV2P; TeSys GV3L; TeSys GV3P; TeSys Deca |
| Control circuit voltage limits | 0.85...1.1 Un |
| [Ui] rated insulation voltage | 690 V AC conforming to IEC 60947-1; 600 V AC conforming to UL 60947-4-1; 600 V AC conforming to CSA C22.2 No 60947-4-1 |
| Threshold tripping voltage | 0.7...0.35 Un |
| Inrush power in VA | 12 VA AC |
| Inrush power in W | 8 W |
| Hold-in power consumption in VA | 3.5 VA AC |
| Hold-in power consumption in W | 1.1 W |
| Operating time | 10...15 ms conforming to IEC 60947-1 |
| On-load factor | 100 % |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²solid; Screw clamp terminals 2 cable(s) 1…2.5 mm²solid; Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end |
| Tightening torque | < 1.4 N.m on screw clamp terminals |
| Mechanical durability | 10000 cycles with GV3P and GV3L; 30000 cycles with GV2ME and GV2P |
| Quantity per set | Set of 10 |
| Height | 89 mm |
| Width | 18 mm |
| Depth | 66 mm |
| Net weight | 0.105 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Product or component type | Undervoltage release |
| Device short name | GVAU |
| [Uc] control circuit voltage | 415...440 V AC 50 Hz; 480 V AC 60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.000 cm |
| Package 1 Width | 8.500 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 115.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 36 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.390 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 576 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 85.240 kg |
The undervoltage release GVAU415 from Schneider Electric belongs to the TeSys and TeSys Deca series and serves as an additional component for motor protection circuit breakers. It enables the safe disconnection of a motor in case of undervoltage or power failure in the control circuit, preventing damage to the installation or the motor. The device is specifically designed for industrial applications where reliable and automatic response to voltage dips is required.
Applications
The GVAU415 is used in conjunction with motor protection circuit breakers from the TeSys family, particularly with models such as GV2ME, GV2LE, GV2L, GV2P, GV3L, and GV3P. It is suitable for installations where motors are operated via control circuits with voltages of 415 to 440 V AC at 50 Hz or 480 V AC at 60 Hz. The application is in industrial environments where continuous power supply for motor control is necessary, for example in manufacturing plants, pump stations, or conveyor systems.
Functions and Equipment in Detail
The undervoltage release reacts to voltage drops in the control circuit and automatically triggers the motor protection circuit breaker when the voltage falls below 70 % of the nominal voltage (Un). The release occurs at a threshold of 0.7 to 0.35 Un, with an operating time between 10 and 15 ms, according to IEC 60947-1. The control circuit voltage ranges from 415 to 440 V AC at 50 Hz and 480 V AC at 60 Hz. The pickup power is 12 VA (8 W) and the holding power consumption is 3.5 VA (1.1 W). These values ensure stable operation without excessive load on the control circuit.
Technology Explained Simply
The GVAU415 is an electromagnetic release connected via screw terminals. The terminals are designed for various cable types: rigid cables with cross-sections from 1 to 2.5 mm², flexible cables without wire ends in the range of 0.75 to 2.5 mm², and flexible cables with wire ends in the range of 0.75 to 1.5 mm². The pickup torque is less than 1.4 Nm, enabling secure and damage-free installation. The mechanical life expectancy is 10,000 cycles when used with GV3P and GV3L, and 30,000 cycles with GV2ME and GV2P, indicating high operational reliability.
Compatibility and Accessories
The undervoltage release is compatible with a wide range of motor protection circuit breakers from the TeSys and TeSys Deca series, including models such as GV2ME, GV2LE, GV2L, GV2P, GV3L, and GV3P. It can be used in combination with motor protection circuit breakers featuring magnetic or thermal tripping. Suitable devices in the range include, for example, the GV3L65, GV2L08, GV2RT21, or GV2ME16, each designed for different rated currents and operating modes.
Mounting and Installation
Mounting is done via the designated screw terminals, designed for various cable cross-sections and types. The maximum depth of the device is 66 mm, height 89 mm, and width 18 mm. The product is finished in dark grey and visually integrates into existing control panels. Installation typically takes place in an enclosure, with electrical connections made according to the specifications of the respective motor protection circuit breaker.
Advantages in Operation
The GVAU415 provides reliable protection against voltage dips, thereby increasing the service life of motors and installations. The low holding power consumption reduces the load on the control circuit. The high mechanical life expectancy and compatibility with various motor protection circuit breakers enhance flexibility in system planning. The rated insulation voltage is 690 V AC (IEC 60947-1) and 600 V AC (UL 60947-4-1 and CSA C22.2 No. 60947-4-1), ensuring safe use in industrial environments.