| Complementary |
| Range compatibility | TeSys GV2ME; TeSys GV2LE; TeSys GV2L; TeSys GV2P; TeSys GV3L; TeSys GV3P; TeSys Deca |
| Control circuit voltage limits | 0.85...1.1 Un |
| [Ui] rated insulation voltage | 690 V AC conforming to IEC 60947-1; 600 V AC conforming to UL 60947-4-1; 600 V AC conforming to CSA C22.2 No 60947-4-1 |
| Threshold tripping voltage | 0.7...0.35 Un |
| Inrush power in VA | 12 VA AC |
| Inrush power in W | 8 W |
| Hold-in power consumption in VA | 3.5 VA AC |
| Hold-in power consumption in W | 1.1 W |
| Operating time | 10...15 ms conforming to IEC 60947-1 |
| On-load factor | 100 % |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²solid; Screw clamp terminals 2 cable(s) 1…2.5 mm²solid; Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end |
| Tightening torque | < 1.4 N.m on screw clamp terminals |
| Mechanical durability | 10000 cycles with GV3P and GV3L; 30000 cycles with GV2ME and GV2P |
| Quantity per set | Set of 10 |
| Height | 89 mm |
| Width | 18 mm |
| Depth | 66 mm |
| Net weight | 0.105 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Product or component type | Undervoltage release |
| Device short name | GVAU |
| [Uc] control circuit voltage | 220...240 V AC 50 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.800 cm |
| Package 1 Width | 8.500 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 108.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 42 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.878 kg |
The GVAU225 is an undervoltage release of the TeSys product line from Schneider Electric, specifically designed for integration into motor protection circuit breakers of the GV2 and GV3 series. It provides protection for electrical installations against unwanted operating conditions during voltage dips or failures. The release is designed for a control circuit voltage of 220 to 240 V AC at 50 Hz and is mounted on the right side of the motor protection circuit breaker. It is compatible with product families TeSys GV2ME, GV2LE, GV2L, GV2P, GV3L, GV3P, as well as TeSys Deca, with particular recommendation for use with GV2ME and GV3P.
Applications
The undervoltage release is used in industrial and commercial installations where safe disconnection is required in case of voltage loss, to protect motors, machines, or entire systems from damage. It is suitable for applications in manufacturing, process technology, and automation technology, where the reliability of power supply is critical. Integration into motor protection circuit breakers enables an integrated protection function directly embedded in the control unit.
Functions and Equipment in Detail
The GVAU225 responds to voltage drops below a defined threshold. The release threshold voltage is between 0.7 and 0.35 times the nominal voltage (Un), with an operating time of 10 to 15 ms. This meets the requirements of standard IEC 60947-1. The pickup power is 12 VA (8 W) and the holding power consumption is 3.5 VA (1.1 W). The mechanical life is 10,000 cycles when used with GV3P and GV3L, and 30,000 cycles with GV2ME and GV2P. Connections are made via screw terminals designed for rigid cables with cross-sections of 1 to 2.5 mm², and flexible cables of 0.75 to 2.5 mm² (without cable end) or 0.75 to 1.5 mm² (with cable end). The tightening torque at the terminals is less than 1.4 Nm.
Technology Explained Simply
The undervoltage release continuously monitors the voltage in the control circuit. When the voltage drops below the predefined threshold, the release is activated and trips the motor protection circuit breaker. This prevents motors from continuing to run under insufficient voltage, which could lead to overheating or mechanical wear. The release function operates quickly and reliably within 10 to 15 ms to minimize damage. The rated insulation voltage is 690 V AC (complies with IEC 60947-1) and 600 V AC (complies with UL 60947-4-1 and CSA C22.2 No. 60947-4-1), ensuring suitability for use in various standard environments.
Compatibility and Accessories
The GVAU225 is suitable for a wide range of motor protection circuit breakers in the TeSys family, particularly models such as GV2ME, GV2P, GV3L, and GV3P. It can be combined with various motor protection circuit breakers, including GV2P21, GV2P03, GV2L06, GV2P14, GV2P04, GV2L08, GV2ME16, GV3L32, GV3P25, GV2ME21, GV3P50, GV2ME07, GV2ME14, GV3L65, GV2L04, GV2P07, GV3P65, GV2P08, GV2L32, and GV2RT07. Combining it with these circuit breakers enables application-specific configuration of protection functions.
Mounting and Installation
Mounting is performed on the right side of the motor protection circuit breaker. The screw terminals allow for secure and easy connection with cables of the specified cross-sections. The dimensions of the device are 89 mm (height), 18 mm (width), and 66 mm (depth). The product weight is 0.105 kg. The color is dark grey, enabling visual integration into existing installations.
Advantages in Operation
The GVAU225 offers reliable and fast response to voltage losses, thereby increasing the operational safety of electrical installations. The high mechanical life and compact design facilitate integration into existing control panels. Compatibility with various motor protection circuit breakers in the TeSys family enables flexible application in different environments. Compliance with international standards such as IEC 60947-1, UL 60947-4-1, and CSA C22.2 No. 60947-4-1 ensures suitability for use in various markets.