| Complementary |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-1; 300 V conforming to UL 508; 300 V conforming to CSA C22.2 No 14 |
| [Ue] rated operational voltage | 24...240 V AC; 24...60 V DC |
| [Ith] conventional free air thermal current | 2.5 A for fault signalling |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB... circuit breaker; GG fuse 10 A |
| Rated operational power in VA | 36 VA at 24 V AC-14 - electrical durability: 1000 cycles at 1.5 A; 48 VA at 48 V AC-14 - electrical durability: 1000 cycles at 1 A; 72 VA at 110…127 V AC-14 - electrical durability: 1000 cycles at 0.5 A; 72 VA at 230…240 V AC-14 - electrical durability: 1000 cycles at 0.3 A |
| Rated operational power in W | 120 W at 240 V DC-13 - electrical durability: 100000 cycles; 140 W at 110 V DC-13 - electrical durability: 100000 cycles; 140 W at 24 V DC-13 - electrical durability: 100000 cycles; 180 W at 60 V DC-13 - electrical durability: 100000 cycles; 240 W at 48 V DC-13 - electrical durability: 100000 cycles; 15 W at 48 V DC-13 - electrical durability: 1000 cycles; 24 W at 24 V DC-13 - electrical durability: 1000 cycles; 9 W at 60 V DC-13 - electrical durability: 1000 cycles |
| Tightening torque | 1.4 N.m screw clamp terminals |
| Height | 89 mm |
| Width | 9.3 mm |
| Depth | 66 mm |
| Net weight | 0.055 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| Standards | EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Device short name | GVAM |
| Product or component type | Auxiliary contact block |
| Product compatibility | GV2P; GV2L; GV2ME; GV2LE; GV2RT; GV2LM; GV3P; GV3L |
| Mounting location | Left side |
| Auxiliary contacts operation | Short-circuit signal 1 C/O |
| Pole contact composition | 1 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 1.5 cm |
| Package 1 Width | 13 cm |
| Package 1 Length | 15 cm |
| Package 1 Weight | 39 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 25 |
| Package 2 Height | 15 cm |
| Package 2 Width | 15 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 1.17 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 800 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 47.44 kg |
Motor protection switches with thermal and magnetic release These devices are easy to use and set up, with compact and ergonomic products for starter motor and stop motor requirements.