| Complementary |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-1; 300 V conforming to UL 508; 300 V conforming to CSA C22.2 No 14 |
| [Ue] rated operational voltage | 48...690 V AC; 24...240 V DC |
| [Ith] conventional free air thermal current | 6 A; 2.5 A for fault signalling |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB... circuit breaker; GG fuse 10 A |
| Rated operational power in W | 120 W at 240 V DC-13 - electrical durability: 100000 cycles; 140 W at 110 V DC-13 - electrical durability: 100000 cycles; 140 W at 24 V DC-13 - electrical durability: 100000 cycles; 180 W at 60 V DC-13 - electrical durability: 100000 cycles; 240 W at 48 V DC-13 - electrical durability: 100000 cycles; 15 W at 48 V DC-13 - electrical durability: 1000 cycles; 24 W at 24 V DC-13 - electrical durability: 1000 cycles; 9 W at 60 V DC-13 - electrical durability: 1000 cycles |
| Height | 89 mm |
| Width | 9.3 mm |
| Depth | 66 mm |
| Net weight | 0.055 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| Product certifications | UKCA |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Device short name | GVAD |
| Product or component type | Auxiliary contact block |
| Product compatibility | GV2ME; GV2L; GV3P; GV2P; GV3L; GV2LE; GV2RT |
| Mounting location | Left side |
| Auxiliary contacts operation | Fault signal 1 NC |
| Pole contact composition | 1 NO + 1 NC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.000 cm |
| Package 1 Width | 8.000 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 43.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 25 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 1.255 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 800 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 47.000 kg |
The GVAD0110 from Schneider Electric is an auxiliary switch block from the TeSys Deca series, specifically designed for supplementary signal transmission on motor protection switches. It serves as an add-on unit for transmitting status and fault signals, particularly during tripping events. The switch is intended for mounting on the left side of compatible motor protection switches and features a configuration consisting of one normally open contact (1 O) and one normally closed contact (1 S), with the normally open contact operating as the fault signal. This configuration enables the actuation of external signals, such as warning lights or relays, whenever a fault occurs in the main device.
Applications
The auxiliary switch block is designed for use in industrial plants where monitoring and signaling of motor protection switches is required. It is frequently used in systems with starter motors or stop motors, where a rapid response to tripping events is necessary. Compatibility with various models such as GV2ME, GV2L, GV3P, GV2P, GV3L, GV2LE, and GV2RT allows for flexible integration into existing systems. Mounting is directly onto the motor protection switch, enabling additional circuits for operational monitoring or alarm signaling.
Functions and Equipment in Detail
The GVAD0110 features a conventional thermal current of 6 A in free air, with the fault signal normally open contact having a thermal current of 2.5 A. The rated operational voltage ranges from 48 to 690 V AC and 24 to 240 V DC, enabling broad applicability in various electrical systems. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, ensuring reliability even under low-load conditions. The mechanical life expectancy is 100,000 cycles, indicating high durability and long service life. The device is dark gray in color, with dimensions of 89 mm (height), 9.3 mm (width), and 66 mm (depth).
Technology Explained Simply
The auxiliary switch block operates as a mechanically coupled accessory that mirrors the state of the main motor protection switch. When the motor protection switch trips, the integrated normally open contact (fault signal) opens, triggering an external signal. The protection type GB2CB – power switch with GG fuse 10 A – ensures safe operation. The rated insulation voltage is 690 V according to IEC 60947-1, allowing use in high-voltage environments. Certification under UKCA confirms compliance with applicable European safety standards.
Compatibility and Accessories
The GVAD0110 is compatible with a wide range of motor protection switches from the TeSys and TeSys Deca series, including models such as GV2P06, GV2RT08, GV2LE14, GV2LE32, GV2P21, GV2L04, GV2LE22, GV2P05, GV2L10, GV2P20, GV2P07, GV2L20, GV2RT10, GV2LE05, GV2ME14, GV3P25, GV2ME08, GV3L32, GV2ME10, and GV3P50. This compatibility allows for flexible selection of main devices based on application requirements. When combined with a motor protection switch, it extends the device’s functionality by enabling external signal transmission, which can be used for process monitoring or alarm signaling.
Mounting and Installation
Mounting is performed on the left side of the motor protection switch, with fastening achieved via integrated connection points. Installation requires no additional tools or components, as the auxiliary switch is directly attached to the main device. Screw terminals ensure a secure and reliable connection. Mounting is carried out under normal environmental conditions, with technical specifications allowing use in industrial plants under standard operating conditions.
Advantages in Operation
Using the GVAD0110 enables precise and reliable signal transmission during tripping events. The high mechanical life of 100,000 cycles ensures long-term operation without maintenance. Compatibility with various motor protection switches from the TeSys and TeSys Deca series offers flexibility in system design. Clear signaling via the fault signal normally open contact supports rapid fault detection and resolution in industrial plants. Compliance with standards IEC 60947-1, UL 508, CSA C22.2 No. 14, and UKCA certification guarantees the safety and reliability of the device.