| Complementary |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-1; 300 V conforming to UL 508; 300 V conforming to CSA C22.2 No 14 |
| [Ue] rated operational voltage | 48...690 V AC; 24...240 V DC |
| [Ith] conventional free air thermal current | 6 A; 2.5 A for fault signalling |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB... circuit breaker; GG fuse 10 A |
| Rated operational power in W | 120 W at 240 V DC-13 - electrical durability: 100000 cycles; 140 W at 110 V DC-13 - electrical durability: 100000 cycles; 140 W at 24 V DC-13 - electrical durability: 100000 cycles; 180 W at 60 V DC-13 - electrical durability: 100000 cycles; 240 W at 48 V DC-13 - electrical durability: 100000 cycles; 15 W at 48 V DC-13 - electrical durability: 1000 cycles; 24 W at 24 V DC-13 - electrical durability: 1000 cycles; 9 W at 60 V DC-13 - electrical durability: 1000 cycles |
| Height | 89 mm |
| Width | 9.3 mm |
| Depth | 66 mm |
| Net weight | 0.055 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| Product certifications | UKCA |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Device short name | GVAD |
| Product or component type | Auxiliary contact block |
| Product compatibility | GV3L; GV2P; GV2LE; GV2RT; GV2L; GV2ME; GV3P |
| Mounting location | Left side |
| Auxiliary contacts operation | Fault signal 1 NC |
| Pole contact composition | 2 NC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 1.500 cm |
| Package 1 Width | 7.000 cm |
| Package 1 Length | 9.000 cm |
| Package 1 Weight | 43.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 25 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 1.276 kg |
The auxiliary switch block GVAD0101 from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for motor protection circuit breakers. It enables the integration of an additional contact for signaling faults or operating conditions. The switch is specifically designed for mounting on the left side of motor protection circuit breakers of types GV3L, GV2P, GV2LE, GV2RT, GV2L, GV2ME, and GV3P. The function of the auxiliary switch is to transmit a fault signal via a normally open contact (1 NO) when the motor protection circuit breaker trips, thereby activating external controls or indicators. The contact configuration includes two normally open contacts (2 NO), one of which serves as the fault signal contact.
Applications
The auxiliary switch block is used in industrial installations where monitoring and signaling of motor protection circuit breaker trips is required. It is suitable for applications in automation technology, such as with pumps, fans, or other drives, where a visual or electrical signal is needed when a protection switch trips. The device is intended for use under normal environmental conditions, without special requirements regarding temperature, humidity, or mechanical stress.
Functions and Equipment in Detail
The GVAD0101 features a mechanical switching contact that closes the normally open contact when the motor protection circuit breaker trips. This contact is rated for an operating voltage of 48 to 690 V AC and 24 to 240 V DC. The rated insulation voltage is 690 V according to IEC 60947-1, enabling use in industrial networks with high voltages. The conventional thermal current is 6 A in free air, while the specific contact for fault indication has a rating of 2.5 A. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, ensuring reliability even under low-load conditions.
Technology Explained Simply
The auxiliary switch operates mechanically and is actuated by the tripping mechanism of the motor protection circuit breaker. When the motor protection circuit breaker trips, the auxiliary switch block is activated and the normally open contact closes to send a signal to an external control or indicator. The protection type GB2CB – power circuit breaker; GG fuse 10 A – indicates that the switch is designed for use in switching installations with power circuit breakers and fuses. The mechanical life is 100,000 cycles, ensuring high operational reliability over a long period. The device is dark gray in color, with dimensions of 89 mm (height), 9.3 mm (width), and 66 mm (depth), allowing for compact integration into existing switching installations.
Compatibility and Accessories
The GVAD0101 is compatible with a wide range of motor protection circuit breakers from the TeSys and TeSys Deca series, including models such as GV2P, GV2LE, GV2RT, GV2L, GV2ME, GV3L, and GV3P. These devices can be combined with various configurations, such as motor protection circuit breakers with rotary drive, push-button operation, or magnetic tripping. This combination allows for flexible adaptation to different requirements in industrial control technology.
Mounting and Installation
Mounting is performed on the left side of the motor protection circuit breaker, with fastening via screw connection. Installation requires no additional tools or special preparations. The mounting dimensions are designed to allow easy integration into standard switch cabinets. The device is intended for use under normal environmental conditions, without special requirements regarding ambient temperature or air humidity.
Advantages in Operation
The use of the GVAD0101 enables reliable signal transmission when the motor protection circuit breaker trips. The high mechanical life and robust construction ensure long-term operational durability. Compatibility with various motor protection circuit breakers from the TeSys series offers flexibility in system design. Clear fault signaling supports maintenance and diagnostics of installations, as the cause of a failure can be identified more quickly. The mounting dimensions and weight (0.055 kg) are designed to allow easy integration into existing switch installations without requiring additional space.