| Complementary |
| Poles description | 3P |
| Utilisation category | Category A conforming to IEC 60947-2 |
| Motor power kW | 90…110 kW at 400/415 V AC 50/60 Hz; 110 kW at 500 V AC 50/60 Hz; 110…132 kW at 660/690 V AC 50/60 Hz |
| Breaking capacity | 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Direct rotary handle |
| [In] rated current | 220 A at 65 °C |
| Magnetic tripping current | 3300 A |
| Rated conditional short-circuit current | 35 kA at 440 V |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 220 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Power dissipation per pole | 17.6 W |
| Mechanical durability | 20000 cycles |
| Electrical durability | 5000 cycles for AC-3 at 415 V opening; 5000 cycles for AC-3 at 415 V closing |
| maximum operating rate | 25 cyc/h |
| Rated duty | Continuous |
| Connection pitch | 35 mm without spreaders |
| Connections - terminals | Bars; Lugs |
| Tightening torque | 15 N.m M8 screw type |
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6; Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Height | 161 mm |
| Width | 105 mm |
| Depth | 155 mm |
| Net weight | 2.6 kg |
| Colour | Anthracite (RAL 7016) |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-1; EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | IECEE CB Scheme; EAC (pending) |
| Climatic withstand | conforming to IACS E10 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for storage | -50…85 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Operating altitude | 5000 m |
| Ambient air temperature for operation | -25…70 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Range of product | TeSys GV5 |
| Device short name | GV5P |
| Product name | TeSys GV5; TeSys Giga |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Electronic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 18.200 cm |
| Package 1 Width | 11.100 cm |
| Package 1 Length | 17.800 cm |
| Package 1 Weight | 2.158 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 14.030 kg |
TeSys GV motor protection circuit breaker, 3 poles (3P), 220A/690V, for the protection of 3-phase motors 90-110kW@400V. It offers thermal magnetic protection and additional protection functions, switching capacity Icu 36kA, start-stop control by rotary handle. Furthermore it offers also connection for rods or cables with cable lugs (direct connection of cables with additional plugs). Thermal protection adjustable via setting wheels with a setting current Ir in the range 100-220A and a selectable trip class 5, 10 or 20, magnetic protection at 15 In. Additional protection functions with fixed tap are short time delay protection Isd at 13 Ir, phase unbalance and failure protection. It provides internal places for additional auxiliary contact blocks (OF, SD) and voltage releases (MN, MX). Certified to multiple standards (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).