| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 30 kW at 400/415 V AC 50/60 Hz; 45 kW at 500 V AC 50/60 Hz; 55 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 65 A |
| Thermal protection adjustment range | 48…65 A conforming to IEC 60947-2 |
| Magnetic tripping current | 910 A |
| [Ith] conventional free air thermal current | 65 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Tightening torque | 5 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Net weight | 0.96 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; ABS; DNV-GL |
| IK degree of protection | IK09 enclosure |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 15 Gn for 11 ms contactor open; Shocks: 30 Gn for 11 ms contactor closed; Vibrations: 4 Gn, 5...300 Hz |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV3 |
| Product or component type | Motor circuit breaker |
| Device short name | GV3P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.400 cm |
| Package 1 Width | 14.600 cm |
| Package 1 Length | 15.700 cm |
| Package 1 Weight | 1.010 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 120 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 131.200 kg |
The
motor protection switch GV3P65 from the
TeSys Deca series by
Schneider Electric is a
motor power switch designed for use in industrial applications. It provides
motor protection functions and safeguards electric motors against overload and short-circuit. The device features a
thermal-magnetic trip unit, integrating both thermal and magnetic protection functions. Operation is performed via a
rotary handle, and the main current connections are equipped with
EverLinkTM terminals, enabling secure and quick connections. The
rated voltage is 690 V AC at 50/60 Hz, with the
operating rated voltage (Ue) also being 690 V AC. The switch is designed for use in
AC networks and complies with usage category
AC-3 according to IEC 60947-4-1 as well as category A according to IEC 60947-2.
Applications include motor protection in industrial drive systems, particularly in installations with a
motor power of 30 kW at 400/415 V AC, 45 kW at 500 V AC, and 55 kW at 690 V AC. The
rated current (In) is 65 A, with the
adjustable range for thermal protection between 48 and 65 A. This allows for adaptable protection according to the specific requirements of the motor. The
magnetic trip current is set at 910 A, ensuring rapid disconnection in case of short-circuit. The
phase failure sensitivity is activated, enabling the switch to respond to a phase failure and protect the motor.
Functions and equipment in detail include the option for
sealing and lockability in the basic version, ensuring safety and control of the operating status. The
screw terminals allow for secure connections, with the
tightening torque for the terminals being 5 Nm. The
loss power per pole is 8 W, indicating efficient heat dissipation. The
mechanical life is 50,000 cycles, and the
electrical life under AC-3 operation at 415 V and rated current is also 50,000 cycles. The
rated power is continuous according to IEC 60947-4-1.
Technology explained simply shows that the switch features a
thermal protection device that disconnects the circuit in case of sustained overload, and a
magnetic protection device that reacts immediately to sudden current surges such as short-circuits. The
EverLinkTM terminals offer quick and secure installation, while the
DIN rail (35 mm symmetrical) and
panel mounting (with 3 x M4 screws) provide flexible installation options. The
protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, while the
protection rating IK09 ensures high mechanical strength against mechanical impacts.
Compatibility and accessories include various extensions that may be required for operation. These include
auxiliary switches such as GVAD1001 (1Sf+1Ö) or GVAD0110 (1Öf+1S),
control circuit trip units such as GVAS055 (48 VAC) or GVAS415 (415–440 VAC), and
under-voltage trip units such as GVAU025 (24 V) or GVAU505 (500 VAC). For parallel supply,
busbars such as GV3G364 (for 3 contactors) or GV3G264 (for 2 contactors) are available.
Rotary drives such as GV3APK01 (IP54, black) or GV3APN04 (IP65, red/yellow) enable mechanical operation. The
suitability for isolation is provided, allowing use in isolated installations.
Mounting and installation is performed on a
35 mm symmetrical DIN rail (clamped) or on a
panel (screwed with 3 x M4 screws). The mounting position can be
horizontal or vertical. Dimensions are
55 mm width, 132 mm height, and 136 mm depth, with the
product weight being 0.96 kg. The
ambient temperature during operation ranges from -20 °C to 60 °C, and during storage from -40 °C to 80 °C. The
operating altitude is permissible up to 3,000 m above sea level. Mechanical robustness is ensured by shock resistance (15 Gn open, 30 Gn closed) and vibration resistance (4 Gn, 5–300 Hz). The
flame resistance is 960 °C according to IEC 60695-2-11.
Operational advantages include high reliability due to the thermal-magnetic trip technology, easy installation thanks to DIN rail and EverLinkTM terminals, and long service life. The integrated phase failure sensitivity increases motor safety. Certifications according to
EN/IEC 60947-2,
EN/IEC 60947-4-1,
UL 60947-4-1,
CSA C22.2 No. 60947-4-1,
ATEX,
LROS,
BV,
ABS,
DNV-GL,
CB Regulation,
CE,
UKCA,
CCC,
cULus,
EAC, and
IEC/EN 60335-1:Clause 30.2 as well as
IEC/EN 60335-2-40:Annex JJ confirm compliance with international standards. The
climate resistance corresponds to IACS E10, enabling use in marine environments.
The
rated impulse voltage withstand is 6 kV, and the
rated insulation voltage (Ui) is 690 V AC. The
breaking capacity (Icu) varies depending on voltage: 100 kA at 230/240 V, 50 kA at 400/415 V and 440 V, 12 kA at 500 V, and 6 kA at 690 V. The
rated operational short-circuit breaking capacity (Ics) is 100 % at 230/240 V, 400/415 V, and 440 V, and 50 % at 500 V and 690 V. The
color of the housing is dark grey.
The switch is designed for use in
industrial applications where reliable and safe motor control and protection are required. The combination of thermal and magnetic protection functions, high protection rating, and diverse mounting and expansion options make it a robust and flexible component in electrical drive systems.