| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 22 kW at 400/415 V AC 50/60 Hz; 30 kW at 500 V AC 50/60 Hz; 45 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 50 A |
| Thermal protection adjustment range | 37…50 A conforming to IEC 60947-2 |
| Magnetic tripping current | 700 A |
| [Ith] conventional free air thermal current | 50 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Tightening torque | 6 N.m - on lugs-ring terminals |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Net weight | 0.96 kg |
| Colour | Dark grey |
| Connection pitch | 17.5 mm without spreaders |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; ABS; DNV-GL |
| IK degree of protection | IK09 enclosure |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 15 Gn for 11 ms contactor open; Shocks: 30 Gn for 11 ms contactor closed; Vibrations: 4 Gn, 5...300 Hz |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV3 |
| Product or component type | Motor circuit breaker |
| Device short name | GV3P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 14.500 cm |
| Package 1 Length | 16.000 cm |
| Package 1 Weight | 922.000 g |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 60 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 63.820 kg |
Motor protection switch up to 30 kW With its new and patented Everlink terminal block system, the TeSys GV3 motor protection switch offers an even more stable and reliable connection quality. The clamping pressure on the cables remains stable, strong and permanently safe, even under difficult conditions. Common accessories for the GV2 and GV3 ranges offer a significant simplification and clear time saving during installation.