| Additional features |
| Pole description | 3P |
| Type of network | AC |
| Application category | Category A corresponds to IEC 60947-2; AC-3 corresponds to IEC 60947-4-1 |
| Network frequency | 50/60 Hz corresponds to IEC 60947-2 |
| Motor power (kW) | 22 kW at 400/415 V AC 50/60 Hz; 30 kW at 500 V AC 50/60 Hz; 45 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz complies with IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz complies with IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz complies with IEC 60947-2; 12 kA Icu at 500 V AC 50/60 Hz complies with IEC 60947-2; 6 kA Icu at 690 V AC 50/60 Hz complies with IEC 60947-2 |
| [Ics] Rated operational short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz complies with IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz complies with IEC 60947-2; 100 % at 440 V AC 50/60 Hz complies with IEC 60947-2; 50 % at 500 V AC 50/60 Hz complies with IEC 60947-2; 50 % at 690 V AC 50/60 Hz complies with IEC 60947-2 |
| Control type | Turn handle |
| [In] Rated current | 50 A |
| Adjustable range for thermal protection | 37…50 A corresponds to IEC 60947-2 |
| Magnetic trip current | 700 A |
| [Ith] conventional thermal current in free air | 50 A corresponds to IEC 60947-2 |
| [Ue] Operational rated voltage | 690 V AC 50/60 Hz complies with IEC 60947-2 |
| [Ui] Rated insulation voltage | 690 V AC 50/60 Hz complies with IEC 60947-2 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947-2 |
| Phase loss sensitivity | Yes, complies with IEC 60947-4-1 |
| Suitability for insulation | Yes, corresponds to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical life | 50000 cycles |
| Electrical lifetime | 50000 cycles for AC-3 at 415 V In |
| Nominal power | Continuous duty, conforms to IEC 60947-4-1 |
| [M] tightening torque | 5 Nm - on screw terminal |
| Mounting mode | 35 mm symmetrical DIN rail: clipped; plate: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Product weight | 0,96 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca |
| Product name | TeSys GV3 |
| Product or component type | Motor power switch |
| Device short name | GV3P |
| Device application | Motor protection |
| Trigger technology | Thermal-magnetic |
| Mounting |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Regulation; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; ABS; DNV-GL |
| Degree of protection (IK) | IK09 enclosure |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Climate resistance | complies with IACS E10 |
| Ambient temperature during storage | -40…80 °C |
| Fire-resistance | 960 °C corresponds to IEC 60695-2-11 |
| Operating ambient temperature | -20…60 °C |
| Mechanical robustness | Shocks: 15 Gn for 11 ms contact open; Shocks: 30 Gn for 11 ms contact closed; Vibrations: 4 Gn, 5 - 300 Hz |
| Operating altitude | 3.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 6,500 cm |
| VPE 1 width | 14,500 cm |
| VPE 1 length | 15,500 cm |
| Packaging weight (Lbs) | 930,000 g |
| VPE 2 type | S06 |
| VPE 2 quantity | 60 |
| VPE 2 height | 75,000 cm |
| VPE 2 width | 60,000 cm |
| VPE 2 length | 80,000 cm |
| VPE 2 weight | 70,000 kg |
Motor protection switch up to 30 kW With its new and patented Everlink terminal block system, the TeSys GV3 motor protection switch offers an even more stable and reliable connection quality. The clamping pressure on the cables remains stable, strong and permanently safe, even under difficult conditions. Common accessories for the GV2 and GV3 ranges offer a significant simplification and clear time saving during installation.