| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 18.5 kW at 400/415 V AC 50/60 Hz; 22 kW at 500 V AC 50/60 Hz; 37 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 40 A |
| Thermal protection adjustment range | 30…40 A conforming to IEC 60947-2 |
| Magnetic tripping current | 560 A |
| [Ith] conventional free air thermal current | 40 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Tightening torque | 5 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Net weight | 0.96 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; ABS; DNV-GL |
| IK degree of protection | IK09 enclosure |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 15 Gn for 11 ms contactor open; Shocks: 30 Gn for 11 ms contactor closed; Vibrations: 4 Gn, 5...300 Hz |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV3 |
| Product or component type | Motor circuit breaker |
| Device short name | GV3P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 14.500 cm |
| Package 1 Length | 16.000 cm |
| Package 1 Weight | 978.000 g |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 120 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 132.840 kg |
TeSys motor protection switch GV3P. Motor protection switch, 3P, thermo-magnetic release. Rated power 18.5 kW, setting range 30-40 A. With thermal and magnetic releases. Sealable and lockable in the basic version. Operation via rotary drive, screw terminals, main current with EverLinkTM terminals. Rated voltage 400 V, according to AC-3.