| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 45 kW at 400/415 V AC 50/60 Hz maximum peak current 750 A; 45 kW at 500 V AC 50/60 Hz maximum peak current 750 A; 55 kW at 690 V AC 50/60 Hz maximum peak current 750 A |
| Breaking capacity | 65 kA Icu at 230/240 V AC 50/60 Hz; 50 kA Icu at 400/415 V AC 50/60 Hz; 50 kA Icu at 440 V AC 50/60 Hz; 12 kA Icu at 500 V AC 50/60 Hz; 6 kA Icu at 690 V AC 50/60 Hz |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz; 60 % at 400/415 V AC 50/60 Hz; 60 % at 440 V AC 50/60 Hz; 50 % at 500 V AC 50/60 Hz; 50 % at 690 V AC 50/60 Hz |
| Control type | Rotary handle |
| [In] rated current | 80 A |
| Magnetic tripping current | 1120 A |
| [Ith] conventional free air thermal current | 80 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 20000 cycles for AC-3 at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Tightening torque | 5 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| Net weight | 0.96 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-1:Clause 30.2; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; EAC; LROS (Lloyds register of shipping); BV; ABS; DNV-GL |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 5 Gn for 11 ms contactor open; Shocks: 30 Gn for 11 ms contactor closed; Vibrations: 4 Gn, 5...300 Hz |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV3 |
| Product or component type | Motor circuit breaker |
| Device short name | GV3L |
| Device application | Motor protection |
| Trip unit technology | Magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.800 cm |
| Package 1 Width | 6.500 cm |
| Package 1 Length | 14.600 cm |
| Package 1 Weight | 1.334 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 16.008 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 120 |
| Package 3 Height | 73.500 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 160.080 kg |
Motor protection switch with magnetic release - TeSys GV3. 3-phase, rated current 80A for a motor power of 45kW at 400V. Conforms to IEC/EN 60947-4-1, EC/EN 60947-2, UL 60947-4-1 and CSA C22.2 No. 60947-4-1. Features such as low-maintenance EverLink terminal technology (removable), optimized width of only 55mm, internally installable auxiliary contacts, lockable in the off position without accessories meet all requirements. For the highest requirements in the area of short-circuit protection. Can be used for motors of all energy efficiency classes IE0 - IE4 up to 14 times the rated current.