| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Toggle |
| [In] rated current | 18 A |
| Thermal protection adjustment range | 13…18 A conforming to IEC 60947-2 |
| Magnetic tripping current | 400 A |
| [Ith] conventional free air thermal current | 18 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1 |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; LROS (Lloyds register of shipping); BV |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2RT |
| Device application | Motor protection; Transformer |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.300 cm |
| Package 1 Width | 4.800 cm |
| Package 1 Length | 8.500 cm |
| Package 1 Weight | 293.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.220 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 128.292 kg |
The
motor protection circuit breaker GV2RT20 from the
TeSys Deca series by
Schneider Electric is a
motor power circuit breaker with
thermal-magnetic tripping technology, designed for the protection of electric motors and transformers. The device features a
toggle switch as the control element and is designed for use in
alternating current (AC) networks with a frequency of
50/60 Hz. It is certified for an
operating voltage rating of 690 V AC and an
insulation voltage rating of 690 V AC, with a
rated impulse voltage withstand of 6 kV. The
rated current (In) is 18 A, with the
adjustable range for thermal protection between 13 and 18 A. The
magnetic trip current is set at 400 A, enabling rapid disconnection under short-circuit conditions. The
rated power is continuous, in accordance with IEC 60947-4-1, and the device meets the application categories
Category A (IEC 60947-2) as well as
AC-3 and AC-3e (IEC 60947-4-1).
Applications include motor protection in drive systems and transformer protection in industrial and commercial installations. The device is suitable for applications requiring reliable disconnection in case of overload or short-circuit. The
breaking capacities vary depending on voltage: 100 kA Icu at 220/230 V, 15 kA at 400/415 V, 8 kA at 440 V, 6 kA at 500 V, and 3 kA at 690 V, in accordance with IEC 60947-2. The
mechanical life is 100,000 cycles, and the
electrical life under AC-3 and AC-3e operation at 415 V and 18 A is also 100,000 cycles.
Functions and equipment in detail include a
3-pole configuration (3P) with
screw terminals for the current circuits. The terminals are designed for
rigid cables from 1 to 6 mm²,
flexible cables without cable ends from 1.5 to 6 mm², and
flexible cables with cable ends from 1 to 4 mm². The
tightening torque is 1.7 Nm. The
power loss per pole is 2.5 W. The device is designed for
mounting on a 35 mm symmetrical DIN rail (coupled) or on a
plate (screwed, with adapter plate). The
mounting position can be horizontal or vertical.
Technology explained simply shows that the
thermal tripping mechanism disconnects the switch in case of sustained overload (within the adjustable range of 13–18 A), while the
magnetic tripping mechanism reacts immediately to sudden, high currents (from 400 A). The
protection class IP20 (according to IEC 60529) protects against finger contact and solid foreign objects, but not against splashing water or dust. The
protection class IK04 provides protection against mechanical impacts such as light shocks. The
climate resistance corresponds to IACS E10, and the
operating ambient temperature ranges from -20 °C to 60 °C, while storage temperature ranges from -40 °C to 80 °C. The
flame resistance is 960 °C in accordance with IEC 60695-2-11.
Compatibility and accessories include various
under-voltage release units (e.g. GVAU125, GVAU025, GVAU207, GVAU415),
auxiliary current release units (e.g. GVAS055, GVAS225, GVAS116, GVAS026, GVAS415),
auxiliary switches (e.g. GVAE1, GVAE20),
connection blocks (e.g. GV1G09),
wiring kits (e.g. GV1G02),
connection blocks (e.g. GV2AF3),
current limiters (e.g. LA9LB920), and
power contactors (e.g. LC1D18E7, LC1D18P7, LC1D18BD). These components can be used to extend functionality and integrate into existing control systems.
Mounting and installation are performed via the DIN rail or a plate with an adapter plate. Dimensions are
45 mm width, 89 mm height, and 78.5 mm depth. Mechanical robustness is ensured by shock resistance (30 Gn for 11 ms) and vibration resistance (5 g, 5–150 Hz). The device complies with standards
EN/IEC 60947-2 and
EN/IEC 60947-4-1 and is certified with
CE, UKCA, CCC, cULus, EAC, LROS, BV.
Operational advantages include
simple operation and adjustment,
compact design, and
high service life. The
thermal-magnetic tripping provides reliable protection against overload and short-circuit. The
compatibility with accessories allows flexible adaptation to specific requirements in industrial installations. The