| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 3 kW at 400/415 V AC 50/60 Hz; 5 kW at 500 V AC 50/60 Hz; 5.5 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 10 A |
| Thermal protection adjustment range | 6…10 A conforming to IEC 60947-2 |
| Magnetic tripping current | 149 A |
| [Ith] conventional free air thermal current | 10 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 2 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 97 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2 |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.700 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 10.200 cm |
| Package 1 Weight | 323.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.764 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 115.056 kg |
The GV2P14 motor protection switch from the TeSys Deca series by Schneider Electric is a
motor power switch designed for use in industrial applications. It provides
motor protection functionality, safeguarding electric motors against overload and short-circuit. The device features
thermal-magnetic tripping technology, which responds to both prolonged overloads and sudden short-circuits. Operation is performed via a
rotary handle, enabling simple and secure actuation. The device is designed for use in
AC networks with a frequency of 50/60 Hz and complies with standards IEC 60947-2 and IEC 60947-4-1.
Applications
The GV2P14 is designed for use in industrial applications, particularly in systems requiring start and stop functions for electric motors. It is suitable for motors with a power rating up to 5.5 kW at 690 V AC, with the exact motor power depending on the operating voltage: 3 kW at 400/415 V AC, 5 kW at 500 V AC, and 5.5 kW at 690 V AC. The protection function also includes
phase failure sensitivity, meaning the device responds to a phase failure in a three-phase network by disconnecting the motor to prevent damage.
Functions and Equipment in Detail
The switch features an
adjustable thermal protection range from 6 to 10 A, allowing it to be adapted to the specific requirements of the motor. The
magnetic tripping current is 149 A, ensuring rapid response under short-circuit conditions. The
rated current (In) is 10 A, and the
conventional thermal current (Ith) in free air is also 10 A. The
rated operational voltage (Ue) is 690 V AC, and the
rated insulation voltage (Ui) is also 690 V AC. The
rated impulse voltage withstand (Uimp) is 6 kV, ensuring high electrical strength under transient voltage surges.
Technology Explained Simply
The
thermal tripping is achieved via a bimetal strip, which triggers the switch when heated due to prolonged overload. The
magnetic tripping is implemented using an electromagnet, which reacts immediately to sudden current increases (e.g., during a short-circuit). The combination of both technologies ensures reliable motor protection. The
power loss per pole is 2.5 W, indicating low heat generation and thus high efficiency. The
mechanical life is 100,000 cycles, and the
electrical life is also 100,000 cycles under AC-3 and AC-3e operation at 415 V and rated current.
Compatibility and Accessories
The GV2P14 can be combined with various accessories to extend its functionality. These include, for example,
load current release units such as GVAS207 or GVAS226,
undervoltage release units such as GVAU115 or GVAU416, and
auxiliary switches such as GVAN20 or GVAD0101. These components enable integration into more complex control systems. Additionally,
connection blocks such as GV2AF3 or adapter plates such as GV2AF02 are available to facilitate mounting on different systems. The
busbar systems GV2G05, GV2G272, GV2G472, and GV2G554 offer flexible connection options for multiple devices.
Mounting and Installation
The switch can be clipped onto a
35 mm symmetrical DIN rail or mounted on a
plate using 2 x M4 screws. Mounting is possible in both
horizontal and vertical positions. The
connection terminals are screw-type and support various cable types: rigid (1–6 mm²), flexible without cable end (1.5–6 mm²), and flexible with cable end (1–4 mm²). The
tightening torque is 1.7 Nm. The device dimensions are
45 mm (width), 89 mm (height), and 97 mm (depth). The housing color is
dark grey.
Operational Advantages
The GV2P14 offers high reliability due to its robust construction and compliance with international standards. The
protection rating IP20 protects against contact with moving parts and against solid foreign objects larger than 12.5 mm. The
protection rating IK04 ensures protection against mechanical impacts such as light shocks. The
operating ambient temperature ranges from -20 °C to 60 °C, and storage is possible from -40 °C to 80 °C. The
flame resistance is 960 °C, ensuring high safety in fire hazard situations. The
climate resistance corresponds to IACS E10, highlighting suitability for marine applications.
Mechanical robustness is ensured by shock resistance (30 Gn for 11 ms) and vibration resistance (5 g, 5–150 Hz). The
certifications include CB regulation, CE, UKCA, CCC, cULus, EAC, ATEX, LROS, BV, RINA, and DNV-GL, confirming international usability.