| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 3 kW at 400/415 V AC 50/60 Hz; 4 kW at 400/415 V AC 50/60 Hz; 4 kW at 500 V AC 50/60 Hz; 5.5 kW at 500 V AC 50/60 Hz; 5.5 kW at 690 V AC 50/60 Hz; 7.5 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Push-button |
| [In] rated current | 10 A |
| Thermal protection adjustment range | 6…10 A conforming to IEC 60947-2 |
| Magnetic tripping current | 149 A |
| [Ith] conventional free air thermal current | 10 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Net weight | 0.26 kg |
| Quantity per set | Set of 24 |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2 |
| Product certifications | CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2ME |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 7.700 cm |
| Package 1 Length | 8.800 cm |
| Package 1 Weight | 256.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.618 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 122.176 kg |
The GV2ME14TQ motor protection switch from the TeSys Deca series by Schneider Electric is a
motor power switch designed for use in industrial applications. It provides
motor protection functionality, safeguarding electric motors against overload and short-circuit. The device is designed for operation in
AC networks and features
thermal-magnetic tripping technology, which responds to both prolonged overloads and sudden short-circuits. Operation is via a
push-button, enabling simple and secure control. The switch is suitable for use in
Category A according to IEC 60947-2, as well as for application categories
AC-3 and
AC-3e per IEC 60947-4-1, qualifying it for use with start-stop motors.
Applications
The GV2ME14TQ is designed for use in industrial installations where reliable protection for electric motors is required. It is particularly suitable for applications with motor powers from 3 to 7.5 kW at various voltages (400/415 V, 500 V, 690 V AC). The protection function includes detection of overloads via a thermal tripping mechanism and rapid disconnection during short-circuits via a magnetic tripping mechanism. The
phase failure sensitivity also enables detection and response to missing phases in the network, which is important for the safety of connected motors.
Functions and Equipment in Detail
The switch features an
adjustable thermal protection range from 6 to 10 A, allowing flexible adaptation to the respective motor power. The
magnetic tripping current is 149 A, ensuring rapid response during short-circuits. The
rated voltage (Ue) is 690 V AC, and the
rated insulation voltage (Ui) is also 690 V AC, ensuring high electrical strength. The
rated impulse withstand voltage (Uimp) is 6 kV, enhancing reliability under transient voltage surges. The
power loss per pole is 2.5 W, limiting thermal load during operation.
Technology Explained Simply
The
thermal-magnetic tripping combines two protection principles: the thermal tripping mechanism responds to continuous overloads by triggering a mechanism via thermal expansion. The magnetic tripping mechanism responds immediately to high current surges, such as those occurring during short-circuits. The
rated current (In) is 10 A, and the
conventional thermal current (Ith) is also 10 A, describing the thermal load capacity of the device. The
breaking capacity ranges from 3 kA to 100 kA Icu depending on voltage, with the
rated service short-circuit breaking capacity (Ics) at 100 %, except at 690 V AC, where it is 75 %. The
mechanical life is 100,000 cycles, and the
electrical life is also 100,000 cycles under AC-3 and AC-3e operation.
Compatibility and Accessories
The switch can be combined with various accessories to extend functionality. These include
auxiliary switches such as GVAD1010 or GVAN11, providing additional contacts for control circuits.
Undervoltage release units like GVAU115 or GVAU225 enable disconnection during voltage drops.
Load current release units such as GVAS385 or GVAS225 offer additional protection functions.
Adapter plates like LAD31 or LAD311 allow mounting on 35 mm DIN rails or for console mounting.
Connection blocks such as GV2AF4 or GV2AF3 are used for connecting to contactors like LC1D09BD.
Connections are made via screw terminals, suitable for rigid cables from 1 to 6 mm² and flexible cables from 1.5 to 6 mm² (without cable end) or 1 to 4 mm² (with cable end). The
tightening torque is 1.7 Nm.
Mounting and Installation
The switch can be
clipped onto a 35 mm symmetrical DIN rail or
screwed to a panel (with adapter plate). The
mounting position can be horizontal or vertical. The
dimensions are 45 mm (width), 89 mm (height), and 78.5 mm (depth). The
product weight is 0.26 kg. The
protection rating (IP) is IP20, providing protection against finger contact and solid foreign objects, but not against water or dust. The
protection rating (IK) is IK04, offering protection against low-intensity mechanical impacts. The
operating ambient temperature ranges from -20 °C to 60 °C, while storage temperature can range from -40 °C to 80 °C. The
flame resistance is 960 °C, according to IEC 60695-2-11. The
climate resistance corresponds to IACS E10. Mechanical robustness is specified with shocks of 30 Gn for 11 ms and vibrations of 5 g in the range 5–150 Hz.
Operational Advantages
The GV2ME14TQ offers high reliability through the combination of thermal and magnetic tripping. Simple operation via push-button and compact design facilitate installation and maintenance. High service life and broad voltage range coverage make it a versatile device for industrial applications. Compatibility with various accessories extends functionality and allows customized adaptation to specific requirements. Certifications according to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC/EN 60335-2-40:Annex JJ, and IEC/EN 60335-1:Clause 30.2, along with product certifications CE, UKCA, CCC, cULus, EAC, ATEX, LROS, BV, and RINA, ensure compliance with international standards and safety requirements.