| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 1.1 kW at 400/415 V AC 50/60 Hz; 1.5 kW at 400/415 V AC 50/60 Hz; 1.5 kW at 500 V AC 50/60 Hz; 2.2 kW at 500 V AC 50/60 Hz; 3 kW at 690 V AC 50/60 Hz; 2.2 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Push-button |
| [In] rated current | 4 A |
| Thermal protection adjustment range | 2.5…4 A conforming to IEC 60947-2 |
| Magnetic tripping current | 74 A |
| [Ith] conventional free air thermal current | 4 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: snap-in terminal 2 cable(s) 0.5…4 mm² - flexible without cable end; Power circuit: snap-in terminal 2 cable(s) 0.5…2.5 mm² - flexible with cable end; Power circuit: snap-in terminal 2 cable(s) (20 AWG...10 AWG) - stranded |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 101 mm |
| Depth | 78.5 mm |
| Net weight | 258 g |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2 |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; ATEX; EU-RO-MR by DNV |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 (on front face) |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2ME |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.600 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 10.500 cm |
| Package 1 Weight | 284.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.968 kg |
The GV2ME08A motor protection switch from the TeSys Deca series by Schneider Electric is a 3-pole motor power switch specifically designed for protecting electric motors in industrial applications. It features a thermomagnetic tripping mechanism that responds to both thermal overloads and magnetic short-circuit currents. Operation is performed via a push-button, ensuring safe and precise control. The device is designed for use in networks with AC supply voltage and complies with standards IEC 60947-2 and IEC 60947-4-1, taking into account usage category A and switching categories AC-3 and AC-3e.
Applications
The GV2ME08A is suitable for use in industrial plants, particularly in drive technology, where reliable motor protection is required. It can be used in systems with an operating voltage up to 690 V AC and a frequency of 50/60 Hz. The motor power covered by this switch reaches up to 3 kW at 690 V AC, with the exact power depending on voltage and network conditions. The protection function also includes phase failure detection, making it suitable for applications requiring high operational safety.
Functions and Equipment in Detail
The switch has an adjustable range for thermal protection from 2.5 to 4 A, with a rated current (In) of 4 A. The magnetic tripping current is 74 A, enabling rapid response to short-circuit currents. The mechanical life is 100,000 cycles, as is the electrical life under AC-3 and AC-3e operation at 415 V. Connections are made via SnapIN terminals, allowing quick and secure connections for cable cross-sections of 0.5 to 4 mm² (flexible without cable end) or 0.5 to 2.5 mm² (flexible with cable end). For stranded cables, cross-sections from AWG 20 to AWG 10 are specified.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping element. The thermal part responds to sustained overloads by tripping the switch via thermal expansion. The magnetic part reacts immediately to high short-circuit currents to prevent damage to the system. The rated voltage is 690 V AC, the rated insulation voltage is also 690 V AC, and the impulse voltage withstand is 6 kV. The operating temperature range is between -20 °C and 60 °C, while the storage temperature range extends from -40 °C to 80 °C. The protection rating IP20 (front) and IK04 (mechanical strength) ensure sufficient protection against mechanical impacts and foreign objects.
Compatibility and Accessories
The GV2ME08A can be combined with various accessories to extend its functionality. These include auxiliary switch blocks such as the GVAE11A (1NC+1NO) or GVAE20A (2 contacts), suitable for front mounting with SnapIN technology. Additionally, power contactors from the LC1D series, such as LC1D09AB7 or LC1D09AF7, can be used in combination with the motor protection switch to realize complex control tasks. Mounting is either on a 35 mm symmetrical DIN rail (clamped) or on a panel (screwed, with adapter plate). The mounting position can be horizontal or vertical.
Mounting and Installation
Installation is performed by securing to a DIN rail or to a panel using an adapter plate. The terminals are designed for SnapIN connections, enabling quick and secure connections. The mechanical robustness of the device is ensured by shock resistance (30 Gn for 11 ms) and vibration resistance (5 g, 5–150 Hz). The device color is dark gray, with dimensions of 45 mm (width), 101 mm (height), and 78.5 mm (depth). The product weight is 258 g.
Advantages in Operation
The GV2ME08A offers high operational safety through mechanically coupled contacts and mirror contacts, making it suitable for safety applications. The SnapIN technology enables maintenance-free and quick electrical connections. The plombable and lockable base version provides additional protection against unauthorized access. Certifications include CB regulation, CE, UKCA, CCC, cULus, ATEX, and EU-RO-MR by DNV, confirming compliance with international standards. The power loss per pole is 2.5 W, ensuring efficient heat generation. The climatic resistance corresponds to IACS E10, and the fire resistance is 960 °C according to IEC 60695-2-11.