| Additional features |
| Subcategory | 1 3-pole contactor; 1 motor protection circuit breaker of type GV2ME; 1 connection block GV2AF01 |
| Coordination type | Type 1 |
| thermal protection adjustment range | 1…1,6 A |
| Breaking capacity | 50 kA Iq at 400/415 V AC 50/60 Hz complies with IEC 60947-4-1; 50 kA Iq at 440 V AC 50/60 Hz complies with IEC 60947-4-1; 50 kA Iq at 500 V AC 50/60 Hz complies with IEC 60947-4-1 |
| Product weight | 0,46 kg |
| Height | 152 mm |
| Width | 45 mm |
| Depth | 87 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Device short name | GV2ME |
| Product or component type | Motor starter |
| Type of motor starter | 1 rotation direction |
| Pole description | 3P |
| Application category | AC-3; AC-3e |
| Motor power (kW) | 0.37 kW at 400/415 V AC 50/60 Hz; 0.55 kW at 400/415 V AC 50/60 Hz; 0.37 kW at 440 V AC 50/60 Hz; 0.55 kW at 440 V AC 50/60 Hz; 0.37 kW at 500 V AC 50/60 Hz; 0.55 kW at 500 V AC 50/60 Hz; 0.75 kW at 500 V AC 50/60 Hz |
| [Uc] control circuit voltage | 24 V DC |
| Magnetic trip current | 22,5 A |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,0 cm |
| VPE 1 width | 15,5 cm |
| VPE 1 length | 8,5 cm |
| Packaging weight (Lbs) | 488,0 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 12 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 30,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 6,203 kg |
Motor protection switches with thermal and magnetic release These devices are easy to use and set up, with compact and ergonomic products for starter motor and stop motor requirements.