| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 0.25 kW at 400/415 V AC 50/60 Hz; 0.37 kW at 400/415 V AC 50/60 Hz; 0.37 kW at 500 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Push-button |
| [In] rated current | 1 A |
| Thermal protection adjustment range | 0.63…1 A conforming to IEC 60947-2 |
| Magnetic tripping current | 15.1 A |
| [Ith] conventional free air thermal current | 1 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Net weight | 0.26 kg |
| Quantity per set | Set of 24 |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2 |
| Product certifications | CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2ME |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.000 cm |
| Package 1 Width | 4.500 cm |
| Package 1 Length | 9.000 cm |
| Package 1 Weight | 211.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.529 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 102.244 kg |
The GV2ME05TQ motor protection switch from the TeSys Deca series by Schneider Electric is a compact device for protecting electric motors. It features a thermomagnetic trip unit that responds to both sustained overloads and sudden short circuits. The devices are designed for use in industrial installations where reliable motor protection is required, particularly during motor start and stop functions.
Applications
This protection switch is designed for use in electrical installations with alternating current (AC) and is suitable for motors with a power rating of 0.25 kW to 0.37 kW at 400/415 V and 500 V AC. The usage category includes Category A according to IEC-2, AC-3 and AC-3e according to IEC-4-1, enabling application with various motor drives, including those with high inrush currents. The operating voltage is up to 690 V AC at 50/60 Hz, allowing the switch to be used in high-voltage installations.
Functions and Equipment in Detail
The switch features a thermal protection with an adjustment range of 0.63 to 1 A, providing protection against sustained overloads. The magnetic trip current is 15.1 A, ensuring rapid disconnection in the event of a short circuit. Phase failure sensitivity is activated, so the switch responds to the loss of a phase. Control is via a push-button, enabling simple operation. The terminals are screw terminals and support cable cross-sections of 1 to 6 mm² (rigid) and 1.5 to 6 mm² (flexible without cable end) and 1 to 4 mm² (flexible with cable end). The tightening torque is 1.7 Nm.
Technology Explained Simply
The thermomagnetic trip unit combines two protection principles: the thermal component responds to continuous overloads by tripping the switch through thermal expansion. The magnetic component reacts immediately to high currents, such as those occurring during short circuits. The rated voltage of 690 V AC and insulation strength of 6 kV ensure safe operation in industrial environments. The impulse voltage withstand of 6 kV protects the device against transient voltage surges. The operating temperature ranges from -20 °C to 60 °C, enabling use in various environments.
Compatibility and Accessories
The protection switch can be combined with various accessories to extend its functionality. These include undervoltage release units such as the GVAU385 (380–400 V) or GVAU225 (220–240 V), which enable disconnection during voltage dips. Auxiliary switches such as the GVAN11 (1NO+1NC, side-mounted) or GVAE11 (front connection) can be used for signal transmission or controlling auxiliary functions. Adapter plates such as the GV2AF02 allow console mounting. Additionally, contactors such as the LC1D09B7 or LC1D09FD are suitable for motor control.
Mounting and Installation
Mounting is either on a 35 mm symmetrical DIN rail (clamped) or on a panel (screwed, with adapter plate). The mounting position can be horizontal or vertical. Dimensions are 45 mm (width), 89 mm (height), and 78.5 mm (depth). The product weight is 0.26 kg. The protection rating is IP20, meaning protection against finger contact and against solid foreign objects, but not against water or dust. The IK protection rating is IK04, providing protection against mechanical impacts such as light shocks.
Advantages in Operation
The protection switch offers reliable motor protection with simple handling. The thermal and magnetic tripping ensures comprehensive protection. Compatibility with accessories extends functionality. Mounting on DIN rail or panel allows flexible installation. The operating temperature range of -20 to 60 °C and high insulation strength make the device suitable for industrial applications. The power loss per pole is 2.5 W, indicating low heat generation. Suitability for insulation according to IEC-1 is provided, enabling use in insulated installations.