| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 5.5 kW at 400/415 V AC 50/60 Hz; 7.5 kW at 500 V AC 50/60 Hz; 9 kW at 690 V AC 50/60 Hz; 11 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Toggle |
| [In] rated current | 14 A |
| Magnetic tripping current | 253.4 A |
| [Ith] conventional free air thermal current | 14 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 1.8 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Net weight | 0.33 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; LROS (Lloyds register of shipping); BV; RINA; DNV-GL |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2LE |
| Device application | Motor protection |
| Trip unit technology | Magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.500 cm |
| Package 1 Width | 9.300 cm |
| Package 1 Length | 4.600 cm |
| Package 1 Weight | 283.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.088 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 124.452 kg |
The GV2LE16 motor protection switch from the TeSys Deca series by Schneider Electric is a motor power switch specifically designed for protecting electric motors in industrial applications. The device features magnetic tripping technology and is designed for use in 3-pole AC networks. It protects motors against overload and short-circuit, with thermal and magnetic tripping ensuring the motor is switched off in case of excessive load or sudden current surges. Operation is via a toggle switch, enabling simple and intuitive handling. The device is rated for operating voltages up to 690 V AC at frequencies of 50/60 Hz and is suitable for applications in industrial automation, particularly for start and stop functions of motors.
Applications
The GV2LE16 is designed for use in industrial environments where reliable motor protection is required. It is commonly used in installations with three-phase motors, particularly in the manufacturing industry, packaging industry, or machine-building industry. The usage category includes Category A according to IEC-2 as well as AC-3 and AC-3e according to IEC-4-1, confirming suitability for start and stop functions with various motor powers. The motor power that can be covered with this switch is 5.5 kW at 400/415 V AC, 7.5 kW at 500 V AC, 9 kW, and 11 kW at 690 V AC. The operating environment must have an ambient temperature between -20 °C and 60 °C, with storage possible between -40 °C and 80 °C.
Functions and Equipment in Detail
The switch features thermal and magnetic tripping, with the magnetic tripping current set at 253.4 A. The thermal tripping protects the motor against overload, while the magnetic tripping responds to sudden short-circuits or high current surges. The rated current is 14 A, with the conventional thermal current in free air also being 14 A. The rated operational voltage (Ue) and rated insulation voltage (Ui) are both 690 V AC. The rated impulse voltage withstand is 6 kV, confirming suitability for environments with high electrical stress. The power loss per pole is 1.8 W, indicating efficient heat dissipation.
Technology Explained Simply
The tripping technology combines thermal and magnetic elements to detect both slow overloads and sudden current surges. The thermal tripping responds to continuous overload by using heat generation within the switch to activate the tripping mechanism. The magnetic tripping reacts immediately to high current values, such as those occurring during short-circuits. The toggle switch allows manual operation, with the state (on/off) being visually identifiable. Screw terminals enable connection of cables with cross-sections of 1 to 6 mm² (rigid) or 1.5 to 6 mm² (flexible without cable end) as well as 1 to 4 mm² (flexible with cable end). The tightening torque is 1.7 Nm to ensure a secure connection.
Compatibility and Accessories
The GV2LE16 is compatible with various accessories that extend its functionality. These include undervoltage release units such as the GVAU385 (380–400 V, 50 Hz) or GVAU115 (110–115 V, 50 Hz), enabling disconnection during voltage dips. Auxiliary switches such as GVAD1001 (1NO+1NC) or GVAD0101 (1NC+1NC) allow integration into control systems. Additionally, load current release units such as GVAS115 (110–115 VAC) or GVAS415 (415–440 VAC) can be used to enable control via external signals. Contactors such as LC1K1201F7 (5.5 kW, 400 V, AC3) can be used in combination with the motor protection switch to complete motor control. The three-phase busbar system GV2G554 (63 A, 5 outlets) offers a modular mounting option.
Mounting and Installation
The switch can be clipped onto a 35 mm symmetrical DIN rail or screwed onto a plate using an adapter plate. Mounting position is possible both horizontally and vertically. Dimensions are 45 mm (width), 89 mm (height), and 78.5 mm (depth), with a product weight of 0.33 kg. The protection rating is IP20, meaning protection against contact with fingers and against solid foreign objects larger than 12.5 mm. The IK04 protection rating provides protection against mechanical impacts such as light shocks. The mechanical life is 100000 cycles, and the electrical life is also 100000 cycles for AC-3 at 415 V In. The ambient temperature during operation is between -20 °C and 60 °C, and during storage between -40 °C and 80 °C. The fire resistance is 960 °C according to IEC-2-11, confirming suitability for safety-critical installations.
Operational Advantages
The GV2LE16 offers reliable motor protection with a compact design and ergonomic operation. The combination of thermal and magnetic tripping ensures comprehensive protection for electric motors. The high rated impulse voltage withstand of 6 kV and suitability for insulation according to IEC-1 increase operational safety. Mounting on DIN rail or plate enables flexible integration into existing installations. Compatibility with various accessories extends functionality and allows customized solutions for different requirements. The operating temperature range of -20 °C to 60 °C makes the device suitable for a wide range of industrial environments. Mechanical robustness with shock resistance of 30 Gn and vibration resistance of 5 g (5–150 Hz) ensures long service life even under harsh operating conditions.