| Complementary |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 15 kW at 400/415 V AC 50/60 Hz; 18.5 kW at 500 V AC 50/60 Hz; 22 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 32 A |
| Magnetic tripping current | 537.6 A |
| [Ith] conventional free air thermal current | 32 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 1.8 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 2 x M4 screws) |
| Mounting position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 97 mm |
| Net weight | 0.33 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; IEC/EN 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CE; UKCA; CCC; EAC; BV; RINA; DNV-GL |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys Deca |
| Product name | TeSys GV2 |
| Product or component type | Motor circuit breaker |
| Device short name | GV2L |
| Device application | Motor protection |
| Trip unit technology | Magnetic |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.900 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 10.200 cm |
| Package 1 Weight | 310.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.441 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 85.292 kg |
The GV2L32 motor protection switch from the TeSys Deca series by Schneider Electric is a motor power switch designed for use in industrial installations. It provides protection for electric motors against overload and short-circuit and is designed for operation in alternating current networks. The device features thermal and magnetic tripping, with the magnetic tripping mechanism activating at a current of 537.6 A. The rated current is 32 A, enabling use with motors up to 15 kW at 400/415 V AC 50/60 Hz. At higher voltages such as 500 V or 690 V AC, higher motor powers of 18.5 kW and 22 kW respectively are possible. The rated operational voltage is 690 V AC, the rated insulation voltage is also 690 V AC, and the rated impulse voltage withstand is 6 kV. The devices are designed for use in networks with a frequency of 50/60 Hz.
Applications
The GV2L32 is designed for use in industrial installations, particularly in systems with start motors and stop motors. It is suitable for category A according to IEC 60947-2 and for usage categories AC-3 and AC-3e according to IEC 60947-4-1. These categories include operation of motors with direct-on-line (DOL) starting and under loads with high starting torque. The devices are intended for use in electrical switchgear where reliable motor protection is required.
Functions and Equipment in Detail
The switch features a rotary handle for control, enabling simple operation. Tripping occurs thermally under overload and magnetically under short-circuit conditions. The thermal tripping responds to continuously increased loads, while the magnetic tripping activates under sudden, high current surges. The mechanical life is 100,000 cycles, and the electrical life is also 100,000 cycles under AC-3 operation at 415 V. The rated power is uninterrupted according to IEC 60947-4-1. The power loss per pole is 1.8 W.
Technology Explained Simply
The thermal tripping is based on a bimetal element that separates the contact when heated due to increased temperature. The magnetic tripping is achieved via an electromagnet that triggers the switch when the preset current value (537.6 A) is exceeded. The protection class IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but not against water or dust. The protection class IK04 protects against mechanical impacts such as light shocks. The ambient temperature during operation ranges from -20 °C to 60 °C, and during storage from -40 °C to 80 °C. The fire resistance is 960 °C according to IEC 60695-2-11.
Compatibility and Accessories
The GV2L32 is compatible with various accessories, including operating current release units such as the GVAS225 (220–240 V 50 Hz) or GVAS026 (24 VAC 60 Hz), undervoltage release units such as the GVAU125 (120–127 VAC 50 Hz) or GVAU207 (200 V 50/60 Hz), and rotary drive sets such as the GV2APN01 (IP54, black) or GV2APN02 (IP54, red). Additionally, busbar systems such as the GV2G445 (63 A, 4 outlets, 45 mm) or GV2G354 (63 A, 3 outlets, 54 mm) are available. Auxiliary switches such as the GVAE1 (1NO or 1NC, front, screw connection) or GVAE20 (2NO, front, screw connection) can be used to extend control functions. Motor protection relays such as the LRD32 (23–32 A, 1NO+1NC, Class 10A) are also compatible.
Mounting and Installation
Mounting is either on a 35 mm symmetrical DIN rail (clamped) or on a panel (screwed with 2 x M4 screws). The mounting position can be horizontal or vertical. The connection terminals are screw terminals designed for rigid cables with 1…6 mm², flexible cables without cable ends with 1.5…6 mm², and flexible cables with cable ends with 1…4 mm². The required tightening torque is 1.7 Nm. The dimensions of the device are 45 mm (width), 89 mm (height), and 97 mm (depth). The product weight is 0.33 kg.
Advantages in Operation
The GV2L32 offers reliable motor protection with high service life and compact design. The simple operation via the rotary handle and clear indication of operating states facilitate use in industrial environments. The high mechanical and electrical service life ensures long-term usability. Compatibility with various accessories allows flexible adaptation to different requirements. Certifications according to CB regulation, CE, UKCA, CCC, EAC, BV, RINA, and DNV-GL guarantee compliance with international standards.