| Complementary |
| Type of operating handle | Direct frontal; External right side; External frontal |
| Mounting support | Plate |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Rated operational power in W | 400 kW at 690 V; 475 kW at 690 V; 560 kW at 400 V; 560 kW at 500 V |
| breaking capacity | 110 W |
| Making capacity | 10000 A at 400 V AC-23B |
| Short-circuit withstand | 90 kA |
| Mechanical durability | 5000 cycles |
| Electrical durability | 100 cycles DC-23A; 100 cycles DC-23B; 500 cycles AC-23A; 500 cycles AC-23B |
| Connections - terminals | Power circuit: bars 80 mm²; Power circuit: lugs-ring terminals 4 cable(s) 185 mm² |
| [Icm] rated short-circuit making capacity | 100 kA at 400 V with protection by gG fuses |
| Tightening torque | Power circuit: 44 N.m |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60947-3 |
| Product certifications | CE |
| IP degree of protection | IP20 conforming to IEC 60529 (with terminal cover) |
| Ambient air temperature for operation | -20…70 °C |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1 |
| Height | 355 mm |
| Width | 442 mm |
| Depth | 289 mm |
| Net weight | 25 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys GS |
| Device short name | GS2V |
| Product or component type | Switch-disconnector-fuse |
| Poles description | 3P |
| Protected poles description | 3t |
| Contacts type and composition | 3 NO |
| [Ith] conventional free air thermal current | 1250 A (at 40 °C) |
| [Ie] rated operational current | 1000 A at 440 V 2 poles in series per phase DC-23A; 1000 A at 440 V 2 poles in series per phase DC-23B; 630 A at 690 V AC-23A; 630 A at 690 V AC-23B; 1000 A at 440 V AC-23A; 1000 A at 440 V AC-23B; 800 A at 500 V AC-23A; 800 A at 500 V AC-23B |
| Fuse type | DIN |
| Fuse size | 4 |
| Network type | AC; DC |
| Network frequency | 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 51.000 cm |
| Package 1 Width | 60.000 cm |
| Package 1 Length | 80.000 cm |
| Package 1 Weight | 40.960 kg |
Fuse switch disconnectors The use of fuses is a reliable and effective solution for protecting your low-voltage equipment against short circuits.