| Complementary |
| Type of operating handle | External frontal |
| Mounting support | Plate |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Rated operational power in W | 450 kW at 400 V; 560 kW at 500 V; 600 kW at 690 V |
| Short-circuit withstand | 200 kA |
| Mechanical durability | 5000 cycles |
| Electrical durability | 1000 cycles |
| Connections - terminals | Power circuit: lugs-ring terminals 2 cable(s) 34…304 mm² |
| Tightening torque | Power circuit: 35 N.m |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 4; UL98 |
| IP degree of protection | IP20 conforming to IEC 60529 (with terminal cover) |
| Ambient air temperature for operation | -20…70 °C |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C body |
| Height | 300 mm |
| Width | 364 mm |
| Depth | 250 mm |
| Net weight | 20.86 kg |
| Main |
| Range | TeSys |
| Product name | TeSys GS |
| Device short name | GS2T |
| Product or component type | Switch-disconnector-fuse |
| Poles description | 3P |
| Protected poles description | 3t |
| Contacts type and composition | 3 NO |
| [Ith] conventional free air thermal current | 800 A (at 40 °C) |
| [Ie] rated operational current | 630 A at 690 V AC-23A; 800 A at 400 V AC-23A; 800 A at 400 V AC-22A; 800 A at 690 V AC-22A |
| Fuse type | UL |
| Fuse size | L |
| Network type | AC; DC |
| Network frequency | 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 44.7 cm |
| Package 1 Width | 41.7 cm |
| Package 1 Length | 52.9 cm |
| Package 1 Weight | 20.86 kg |
Fuse switch disconnectors The use of fuses is a reliable and effective solution for protecting your low-voltage equipment against short circuits.