| Complementary |
| Type of operating handle | External frontal; External right side |
| Mounting support | Plate |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Rated operational power in W | 80 kW at 400 V; 110 kW at 500 V; 110 kW at 690 V |
| Making capacity | 1600 A at 400 V AC-23B |
| Breaking capacity | 1280 A at 400 V (AC-23B) |
| Short-circuit withstand | 22.7 kA |
| Mechanical durability | 10000 cycles |
| Electrical durability | 1000 cycles AC-23A; 1000 cycles AC-23B; 200 cycles DC-23A; 200 cycles DC-23B |
| Connections - terminals | Power circuit: bars 20 mm²; Power circuit: lugs-ring terminals 50…95 mm² |
| [Icm] rated short-circuit making capacity | 100 kA at 400 V with protection by gG fuses |
| Tightening torque | Power circuit: 12 N.m |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60947-3 |
| Product certifications | CE |
| IP degree of protection | IP20 conforming to IEC 60529 (with terminal cover) |
| Ambient air temperature for operation | -20…70 °C |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1 |
| Height | 162 mm |
| Width | 184 mm |
| Depth | 126.5 mm |
| Net weight | 2.3 kg |
| Logistical informations |
| Country of origin | TN |
| Main |
| Range | TeSys |
| Product name | TeSys GS |
| Device short name | GS2L |
| Product or component type | Switch-disconnector-fuse |
| Poles description | 4P |
| Protected poles description | 4t |
| Contacts type and composition | 4 NO |
| [Ith] conventional free air thermal current | 160 A (at 40 °C) |
| [Ie] rated operational current | 125 A at 440 V 2 poles in series per phase DC-23A; 125 A at 440 V 2 poles in series per phase DC-23B; 125 A at 690 V AC-23A; 125 A at 690 V AC-23B; 160 A at 400 V AC-23A; 160 A at 400 V AC-23B; 160 A at 500 V AC-23A; 160 A at 500 V AC-23B |
| Fuse type | DIN |
| Fuse size | 00 |
| Network type | DC; AC |
| Network frequency | 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.5 cm |
| Package 1 Width | 17.0 cm |
| Package 1 Length | 21.0 cm |
| Package 1 Weight | 2.258 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 40.0 cm |
| Package 2 Length | 60.0 cm |
| Package 2 Weight | 7.577 kg |
Fuse switch disconnectors The use of fuses is a reliable and effective solution for protecting your low-voltage equipment against short circuits.