| Complementary |
| Mechanical durability | 1 Mcycles |
| Electrical durability | 30000 cycles AC-15 |
| switch rated current | 50 A; 63 A; 100 A; 125 A; 160 A; 200 A; 250 A; 315 A; 400 A |
| Fuse type | NFC; DIN; BS |
| Type of operating handle | Direct right side |
| Mounting location | Front face |
| Net weight | 0.035 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys |
| Device short name | GS1AM |
| Product or component type | Auxiliary contact |
| Contact application | O and I position signalling |
| Range compatibility | TeSys TeSys GS GS1 F fuse-switch disconnector; TeSys TeSys GS GS1G fuse-switch disconnector; TeSys TeSys GS GS1 J fuse-switch disconnector; TeSys TeSys GS GS1 K fuse-switch disconnector; TeSys TeSys GS GS1 L fuse-switch disconnector; TeSys TeSys GS GS1 N fuse-switch disconnector; TeSys TeSys GS GS1Q fuse-switch disconnector |
| Contacts type and composition | 2 C/O |
| Contact operation | Early-break |
| [Ith] conventional free air thermal current | 16 A (at 40 °C) |
| [Ie] rated operational current | 5 A at 127 V AC-15; 4 A at 230 V AC-15; 3 A at 400/415 V AC-15; 2 A at 440 V AC-15; 12 A at 24 V DC-13; 2 A at 48 V DC-13; 0.6 A at 110 V DC-13; 0.4 A at 220 V DC-13 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 3.000 cm |
| Package 1 Length | 10.000 cm |
| Package 1 Weight | 39.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 973.000 g |
Fuse switch disconnectors The use of fuses is a reliable and effective solution for protecting your low-voltage equipment against short circuits.