| Complementary |
| Utilisation category | AC-7B; AC-7A |
| Poles description | 4P |
| power pole contact composition | 4 NC |
| [Ie] rated operational current | 25 A AC-7A; 8.5 A AC-7B |
| Operating position | 30°/vertical |
| Control circuit type | AC at 50 Hz |
| [Uc] control circuit voltage | 220...240 V AC 50 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| [Ith] conventional free air thermal current | 25 A (at 50 °C) for power circuit |
| Irms rated making capacity | 68 A at 400 V AC for power circuit conforming to IEC 61095 |
| Rated breaking capacity | 68 A at 400 V for power circuit conforming to IEC 61095 |
| [Icw] rated short-time withstand current | 200 A 40 °C - 10 s for power circuit; 62 A 40 °C - 30 s for power circuit |
| Associated fuse rating | 25 A gL at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | 500 V conforming to IEC 61095; 500 V conforming to VDE 0110 |
| Electrical durability | AC-7A: 100000 cycles; AC-7B: 100000 cycles |
| Power dissipation per pole | 1.6 W |
| Control type | Remote control |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Standards | IEC 60947-5; IEC 61095 |
| Tightening torque | Control circuit: 0.8 N.m - on screw clamp terminals; Power circuit: 0.8 N.m - on screw clamp terminals |
| Operating time | 10...25 ms opening; 10...30 ms closing |
| Mechanical durability | 1000000 cycles |
| Maximum operating rate | 300 cyc/h 50 °C |
| Control circuit voltage limits | Drop-out: 0.2...0.75 Uc at 50 Hz (at |
| Inrush power in VA | 34 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA | 4.6 VA 50 Hz (at 20 °C) |
| Heat dissipation | 1.6 W at 50/60 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP40 conforming to VDE 0106 (in enclosure); IP20 conforming to VDE 0106 |
| Protective treatment | TC |
| Ambient air temperature for operation | -5…50 °C |
| Ambient air temperature for storage | -40…70 °C |
| Mechanical robustness | Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms; Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 3 Gn, 5...300 Hz |
| Total number of 18 mm modules | 2 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 62.5 mm |
| Net weight | 0.23 kg |
| Quantity per set | Set of 6 |
| Colour | White |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys GC |
| Product or component type | Modular contactor |
| Device short name | GC25 |
| Contactor application | Motor control; Lighting; Heating |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8 cm |
| Package 1 Width | 9.5 cm |
| Package 1 Length | 23 cm |
| Package 1 Weight | 206 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 8 cm |
| Package 2 Width | 9.5 cm |
| Package 2 Length | 23 cm |
| Package 2 Weight | 1.292 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 10.835 kg |
TeSys GC contactor for general applications such as lighting, heating, ventilation. It offers 4 NC poles with a nominal voltage of 25 A/415 V AC, a 220-240 V AC 50 Hz coil, screw terminals and a status indicator on the front. For use in modular control panels and enclosures, width of 2 modules (36 mm), quick fixing on DIN rail. It complies with IEC standards, is certified NF-USE, VDE, CEBEC, OVE and Green Premium (RoHs/Reach).