| Complementary |
| Utilisation category | AC-7A; AC-7B |
| Poles description | 2P |
| power pole contact composition | 2 NO |
| [Ie] rated operational current | 16 A AC-7A; 5 A AC-7B |
| Operating position | 30°/vertical |
| Control circuit type | AC at 50 Hz |
| [Uc] control circuit voltage | 24 V AC 50 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| [Ith] conventional free air thermal current | 16 A (at 50 °C) for power circuit |
| Irms rated making capacity | 40 A at 400 V AC for power circuit conforming to IEC 61095 |
| Rated breaking capacity | 40 A at 400 V for power circuit conforming to IEC 61095 |
| [Icw] rated short-time withstand current | 128 A 40 °C - 10 s for power circuit; 40 A 40 °C - 30 s for power circuit |
| Associated fuse rating | 16 A gL at |
| Average impedance | 2.5 mOhm - Ith 16 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | 500 V conforming to IEC 61095; 500 V conforming to VDE 0110 |
| Electrical durability | AC-7A: 100000 cycles; AC-7B: 100000 cycles |
| Power dissipation per pole | 0.65 W |
| Control type | Remote control |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Standards | IEC 60947-5; IEC 61095 |
| Tightening torque | Control circuit: 0.8 N.m - on screw clamp terminals; Power circuit: 0.8 N.m - on screw clamp terminals |
| Operating time | 10...25 ms opening; 10...30 ms closing |
| Mechanical durability | 1000000 cycles |
| Maximum operating rate | 300 cyc/h 50 °C |
| Control circuit voltage limits | Drop-out: 0.2...0.75 Uc at 50 Hz (at |
| Inrush power in VA | 15 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA | 3.8 VA 50 Hz (at 20 °C) |
| Heat dissipation | 1.3 W at 50/60 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP40 conforming to VDE 0106 (in enclosure); IP20 conforming to VDE 0106 |
| Protective treatment | TC |
| Ambient air temperature for operation | -5…50 °C |
| Ambient air temperature for storage | -40…70 °C |
| Mechanical robustness | Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms; Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 3 Gn, 5...300 Hz |
| Total number of 18 mm modules | 1 |
| Height | 81 mm |
| Width | 17.5 mm |
| Depth | 62.5 mm |
| Net weight | 0.11 kg |
| Quantity per set | Set of 12 |
| Colour | White |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys GC |
| Product or component type | Modular contactor |
| Device short name | GC16 |
| Contactor application | Heating; Motor control; Lighting |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.000 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 23.000 cm |
| Package 1 Weight | 114.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 2.900 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 20.000 cm |
| Package 2 Weight | 1.433 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 96 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 12.156 kg |
TeSys GC modular contactor, 2 poles (2NO), 16A/250V AC-7a (heating) and 5A/250V AC-7b (motor control), for domestic applications. Control voltage 24V AC 50Hz, status indicator on the front. For use in modular control panels, compact (18mm width), snaps onto 35mm DIN rail, connection via screw terminals. Sold in batches of 12 units. Multi-standard certified (IEC, EN, NF-USE, VDE, CEBEC, OVE), Green Premium compliant (RoHS/REACh).