Further information for Schneider Electric GB2CB05 power switch 1-pole 0.5 A
TeSys GB circuit breaker, 1 pole, 0.5 A/250 V, IEC/277 V UL, for the protection of industrial control circuits. It offers thermo-magnetic protection with a magnetic tripping current at 6.6 A (13-14 In) and a breaking capacity Icu 50kA@240V. Compact device (15 mm wide) with toggle control and quick fixing on DIN rail. It complies with several standards (IEC, UL, CSA, NEMKO) and Green Premium (RoHs/Reach).