| Additional features |
| Type of auxiliary contacts | Standard |
| [Ith] conventional thermal current in free air | 5 A |
| [Ie] Rated operational current | AC-12: 3 A at 250 V AC 50/60 Hz; AC-12: 5 A at 125 V AC 50/60 Hz; AC-12: 5 A at 24 V AC 50/60 Hz; AC-12: 5 A at 48 V AC 50/60 Hz; AC-15: 2 A at 250 V AC 50/60 Hz; AC-15: 3 A at 125 V AC 50/60 Hz; AC-15: 5 A at 24 V AC 50/60 Hz; AC-15: 5 A at 48 V AC 50/60 Hz; DC-12: 0.2 A at 250 V DC; DC-12: 0.4 A at 125 V DC; DC-12: 2.5 A at 48 V DC; DC-12: 4 A at 24 V DC; DC-14: 0.2 A at 250 V DC; DC-14: 0.4 A at 125 V DC; DC-14: 1 A at 48 V DC; DC-14: 3 A at 24 V DC |
| Minimum load | 10 mA at 24 V |
| Auxiliary terminal clamp | Lead wire |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | EasyPacT CVS; EasyPact EZC; GoPact R MCCB |
| Device short name | EZC100; CVS100BS; GR12T |
| Product or component type | Switch |
| Device application | Signalling |
| Compatible product family | EasyPacT EasyPacT CVS CVS100BS circuit breaker; EasyPacT EasyPact EZC EZC100; GoPact R MCCB GR12T |
| Signal contact composition | 1 normally open contact (NO) / normally closed contact (NC) |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 2,5 cm |
| VPE 1 width | 7,0 cm |
| VPE 1 length | 8,5 cm |
| Packaging weight (Lbs) | 40,0 g |
This is an auxiliary switch (AX) as part of the indicator contact for the EasyPact EZC100 circuit breaker. The AX indicates the position of the circuit breaker contacts. The contact status is indicated by the remote ON or OFF indication. These electrical aids are locked in place when the front cover is opened.