| Additional features |
| Coil technology | With integrated suppression unit |
| [Uimp] Rated impulse voltage withstand | 8 kV |
| [Ith] conventional thermal current in free air | 20 A (at 50 °C) |
| [Irms] Rated making capacity | 110 A at 690 V complies with IEC 60947; 110 A at 690 V complies with NF C 63-110 |
| [Icw] rated short-time current withstand | 90 A 50 °C - 1 s; 85 A 50 °C - 5 s; 80 A 50 °C - 10 s; 60 A 50 °C - 30 s; 45 A 50 °C - 1 min; 40 A 50 °C - 3 min; 20 A 50 °C - >= 15 min. |
| Associated fuse | 10 A gG compliant with IEC 60947; 10 A gG compliant with VDE 0660 |
| [Ui] Rated insulation voltage | 690 V corresponds to IEC 60947; 750 V corresponds to VDE 0110 Group C; 690 V corresponds to BS 5424 |
| Mounting bracket | Plate; rail |
| Connections - terminals | Ring terminal connectors (outer diameter: 7 mm) |
| Tightening moment | Power circuit: 1.1 Nm - on ring terminal lugs - with Phillips screwdriver No. 23,2 mm; power circuit: 1.1 Nm - on ring terminal lugs - with flat screwdriver Ø 63,2 mm; power circuit: 1.1 Nm - on ring terminal lugs - with screwdriver position No. 2 |
| Control circuit voltage limits | Operation: 0.7 - 1.3 Uc (at |
| Operating time | 10 - 20 ms coil energization and NO opening; 15 - 25 ms coil de-energization and NC contact closing; 30 - 40 ms coil energization and NO closing; 25 - 35 ms coil energization and NC opening |
| Mechanical life | 30 Mcycles |
| Max. operating rate | 6000 cyc/h |
| Immunity to interruptions | 2 ms |
| Absorption power in W | 1.8 W (at 20 °C) |
| Holding power consumption in W | 1.8 W at 20 °C |
| Heat emission | 1,8 W |
| Min. switching voltage | 17 V |
| Min. switching current | 5 mA |
| Non-overlapping distance | 0,5 mm |
| Insulation resistance | > 10 MΩ |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Product weight | 0,235 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CAK |
| Application of contactor | Control circuit |
| Application category | DC-13; AC-15 |
| Pole description | 4P |
| Composition of pole contact | 3 S + 1 Ö |
| Control circuit type | DC low power consumption |
| [Uc] control circuit voltage | 110 V DC |
| Mounting |
| Standards | BS 5424; IEC 60947; VDE 0660; IEC 60077-1; IEC 60077-2; EN 45545: R22 HL3; NF C 63-110; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 Nr. 60947-4-1 |
| Product certifications | CB certification; CCC; UL; CSA; EAC; CE; UKCA |
| Degree of protection (IP) | IP20 corresponds to VDE 0106 |
| Coating | TC corresponds to IEC 60068; TC corresponds to DIN 50016 |
| Operating ambient temperature | -25…50 °C |
| Ambient temperature during storage | -50…80 °C |
| Operating altitude | 2,000 m without derating |
| Flame retardancy | V0 corresponds to UL 94 |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,7 cm |
| VPE 1 width | 4,8 cm |
| VPE 1 length | 6,2 cm |
| Packaging weight (Lbs) | 240,0 g |