| Additional features |
| Application category | AC-14; AC-15 |
| Composition of pole contact | 3 S + 1 Ö |
| Control circuit type | AC at 50 Hz |
| Rated operating voltages [Uc] | 220 V AC 50 Hz |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| [Ith] conventional thermal current in free air | 10 A (at 40 °C) |
| [Irms] Rated making capacity | 140 A at 690 V AC complies with IEC 60947-5-1 |
| [Icw] rated short-time current withstand | 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse | 10 A gG at 690 V complies with IEC 60947-5-1 |
| [Ui] Rated insulation voltage | 690 V corresponds to IEC 60947-5-1 |
| Mounting bracket | Plate; rail |
| Connections - terminals | Screw terminals 1 1…2.5 mm² - Cable grip: flexible without cable end; Screw terminals 2 1…2.5 mm² - Cable grip: flexible without cable end; Screw terminals 1 1…2.5 mm² - Cable grip: flexible with cable end; Screw terminals 2 1…2.5 mm² - Cable grip: flexible with cable end; Screw terminals 1 1…2.5 mm² - Cable grip: solid without cable end; Screw terminals 2 1…2.5 mm² - Cable grip: solid without cable end |
| Recommended tightening torque | 1.2 Nm - on screw terminals - with Phillips screwdriver No. 2 |
| Control circuit voltage limits | Operation: 0.85 - 1.1 Uc at 50 Hz; Dropout voltage: 0.3 - 0.6 Uc |
| Operating time | 4 - 19 ms coil energizing and NC opening; 12 - 22 ms coil energizing and NO closing; 4 - 12 ms coil de-energizing and NC opening; 6 - 17 ms coil de-energizing and S closing |
| Mechanical life | 10 Mcycles |
| Max. operating rate | 180 cyc/mn |
| Input power in VA | 70 VA 50 Hz (at 20 °C) |
| Hold power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Min. switching voltage | 17 V |
| Min. switching current | 5 mA |
| Non-overlapping time | 1.5 ms when actuated between normally open contact and normally closed contact; 1.5 ms when de-energized between normally open contact and normally closed contact |
| Insulation resistance | > 10 MΩ |
| Mechanical robustness | Shocks control relay open: 7 Gn for 11 ms; shocks control relay closed: 10 Gn for 11 ms; vibrations control relay open: 1.5 Gn, 5 - 300 Hz; vibrations control relay closed: 3 Gn, 5 - 300 Hz |
| Height | 74 mm |
| Width | 45 mm |
| Depth | 80 mm |
| Product weight | 0,28 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Easy TeSys |
| Product or component type | Control relay |
| Device short name | CAE |
| Application of contactor | Control circuit |
| Colour | Grey (RAL 7011) |
| Mounting |
| Standards | EN/IEC 60947-1; EN/IEC 60947-5-1; GB/T 14048.1; GB/T 14048.5; IS/IEC 60947-1; IS/IEC 60947-5-1 |
| Product certifications | CB Scheme; CCC; CE; EAC; BIS |
| Degree of protection (IP) | IP2x complies with IEC 60529 |
| Coating | TH corresponds to IEC 60068 |
| Operating ambient temperature | -20…70 °C |
| Ambient temperature during storage | -60…80 °C |
| Operating altitude | 3,000 m without power derating |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,000 cm |
| VPE 1 width | 7,500 cm |
| VPE 1 length | 8,500 cm |
| Packaging weight (Lbs) | 293,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 36 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 10,842 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 576 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 181,472 kg |