| Additional features |
| Contact control | Mechanically linked, complies with IEC 60947-5-1 |
| Control circuit voltage limits | Drop voltage: 0.3 - 0.6 Uc; Operation: 0.8 - 1.1 Uc at 50 Hz; Operation: 0.85 - 1.1 Uc at 60 Hz |
| Creepage voltage Ui | 600 V - Certifications CSA; 600 V - Certifications UL; 690 V - Overvoltage category III (pollution degree 3) - according to IEC 60947-5-1 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Torque | 1,7 Nm |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) |
| [Irms] Rated making capacity | 140 A at |
| Associated fuse | 10 A gG |
| Input power in VA | 70 VA (at 20 °C) |
| Hold power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Mechanical life | 30000000 cycles |
| Max. operating rate | 3 cyc/s 20 °C |
| Response time | 12 - 22 ms coil energizing and NO closing; 4 - 12 ms coil de-energizing and NO opening; 4 - 19 ms coil energizing and NC opening; 6 - 16 ms coil de-energizing and NC closing |
| Min. switching current | 5 mA |
| Min. switching voltage | 17 V |
| Insulation resistance | > 10 MΩ |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Product weight | 0,58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product name | TeSys CAD; TeSys Deca |
| Product or component type | Auxiliary contactor |
| Device short name | CAD |
| Application of contactor | Control circuit |
| Application category | AC-15; AC-14 |
| Control circuit type | AC |
| Coil type | Standard |
| Suppression technology | Without installation |
| Composition of pole contact | 5 NO |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Connections - terminals | 1 cable(s) 1…4 mm² flexible with cable end; 1 cable(s) 1…4 mm² flexible without cable end; 1 cable(s) 1…4 mm² solid without cable end; 2 cable(s) 1…2.5 mm² flexible with cable end; 2 cable(s) 1…4 mm² flexible without cable end; 2 cable(s) 1…4 mm² solid without cable end |
| Quantity per set | Set of 10 pieces |
| Mounting |
| Standards | BS 4794; IEC 60947-5-1; NF C 63-140; EN 60947-5; VDE 0660; IEC 60335-1 |
| Product certifications | CSA; UL; UKCA |
| Degree of protection (IP) | IP2x corresponds to VDE 0106 |
| Coating | TH corresponds to IEC 60068 |
| Operating ambient temperature | -40…70 °C at Uc; -5…60 °C at 0.8-1.1 Uc |
| Ambient temperature during storage | -60…80 °C |
| Operating altitude | 3,000 m without power derating |
| Shock resistance | 10 Gn control relay open; 15 Gn control relay closed |
| Vibration resistance | 2 Gn 5…300 Hz control relay open; 4 Gn 5…300 Hz control relay closed |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 4,5 cm |
| VPE 1 width | 7,7 cm |
| VPE 1 length | 8,6 cm |
| Packaging weight (Lbs) | 12,0 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 24 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 30,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 743,0 g |
Standard contactors 0.06 -75 kW In addition to an attractive and functional design, the TeSys D contactors offer quick and easy installation with a narrow width of 45 or 55 mm. They meet international standards. The power sizes 40 to 65 A are equipped with EverLink terminals. These are patented and ensure a reliable and permanent connection.