| Complementary |
| Utilisation category | AC-15; AC-14; DC-13 |
| Pole contact composition | 5 NO |
| Control circuit type | DC low consumption |
| [Uc] control circuit voltage | 24 V DC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC; 250 A DC |
| [Icw] rated short-time withstand current | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 |
| Mounting support | Rail; Plate |
| Connections - terminals | Snap-in terminal 1 cable(s) 0.5…4 mm²flexible without cable end; Snap-in terminal 2 cable(s) 0.5…4 mm²flexible without cable end; Snap-in terminal 1 cable(s) 0.5…2.5 mm²flexible with cable end; Snap-in terminal 2 cable(s) 0.5…2.5 mm²flexible with cable end |
| Operating time | 65...88 ms coil energisation and NO closing; 14...25 ms coil de-energisation and NO opening |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Time constant | 40 ms |
| Inrush power in W | 2.4 W (at 20 °C) |
| Hold-in power consumption in W | 2.4 W at 20 °C |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact; 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 107 mm |
| Width | 45 mm |
| Depth | 93 mm |
| Net weight | 562 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; JIS C8201-5-1 |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.700 cm |
| Package 1 Width | 11.500 cm |
| Package 1 Length | 10.000 cm |
| Package 1 Weight | 578.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.020 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 153.220 kg |
The
control relay CAD50ABL of the
TeSys series by
Schneider Electric is an auxiliary contactor for use in control circuits. It features five
closing contacts (5S) and a
coil with 24 V DC, designed for low power consumption. The device is designed for demanding industrial applications requiring high operating speeds and reliability. The maximum operating rate is 180 cycles per minute, equivalent to up to 10800 cycles per hour. The mechanical life expectancy is 30 million switching cycles, ensuring high durability even under intensive use.
Applications
This relay is intended for use in control systems in industrial environments, particularly in applications requiring high switching frequencies. It is suitable for applications in automation technology, such as in manufacturing, packaging technology, or machine control. The usage categories include AC-15, AC-14, and DC-13, with a maximum insulation voltage of 690 V. The rated impulse voltage withstand is 6 kV, ensuring high electrical strength even under transient voltage surges.
Functions and Features in Detail
The device features integrated
Snap-IN connection terminals, enabling fast, secure, and maintenance-free cable connections. The terminals are designed for flexible cables with cross-sections of 0.5 to 4 mm² without wire ends and 0.5 to 2.5 mm² with wire ends. The contacts are mechanically coupled, ensuring a secure and reliable switching function. The non-overlapping time is 1.5 ms during energizing and de-energizing between closing and opening contacts, ensuring precise switching operations. The operating time is 65–88 ms for coil energizing and NO closing, and 14–25 ms for coil de-energizing and NO opening.
Technology Explained Simply
The relay coil is operated at 24 V DC and consumes 2.4 W for pickup and 2.4 W for holding at 20 °C. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA. The relay time constant is 40 ms, influencing switching speed and stability. The conventional thermal current rating is 10 A at an ambient temperature of 60 °C. The rated make capacity is 140 A for AC and 250 A for DC. The rated short-time current withstand is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms. The associated fuse is a 10 A gG fuse according to IEC 60947-5-1.
Compatibility and Accessories
The relay can be expanded with up to nine additional auxiliary contacts. Compatible accessories include various auxiliary switch blocks such as LADN02A (2 opening contacts, Snap-IN), LADN11A (1 closing + 1 opening, Snap-IN), LADN20A (2 closing, Snap-IN), as well as delayed auxiliary switch blocks like LAD-R4 (delayed reset, 10–180 seconds) and LAD-S2 (delayed pickup, 1–30 seconds). Time blocks such as LADR0 (0.10–3.00 s), LADR2 (1–30.00 s), LADT0 (0.10–3.00 s, delayed pickup), and LADT2 (0.10–30.00 s, delayed pickup) can also be integrated. Mounting options include both rail and panel mounting.
Mounting and Installation
The relay can be mounted on a mounting rail or directly on a panel. Dimensions are 107 mm (height), 45 mm (width), and 93 mm (depth). The product weight is 562 g. Mounting complies with standards EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. The protection rating is IP2x on the front, representing a touch protection class according to VDE 0106. The coating corresponds to category TH according to IEC 60068.
Operational Advantages
The relay features high mechanical robustness, with shock resistance of 10 Gn (open) and 15 Gn (closed) for 11 ms, and vibration resistance of 2 Gn (open) and 4 Gn (closed) in the frequency range of 5–300 Hz. The operating temperature range is from -40 °C to 60 °C, with performance reduction required at temperatures from 60–70 °C. The storage temperature range is from -60 °C to 80 °C. The operating altitude is up to 3000 m above sea level. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation. Product standards and certifications include CB Regulation, CCC, cULus, CE, UKCA, and EU-RO-MR by DNV.
Suitable for Safety Applications
Due to the mechanical coupling of contacts and the use of mirror contacts, the relay is suitable for safety applications requiring secure and reliable switching functions. The design ensures that contacts switch synchronously, which is important for reliability in critical control systems.