| Complementary |
| Utilisation category | DC-13; AC-15; AC-14 |
| Pole contact composition | 3 NO + 2 NC |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 480 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| [Icw] rated short-time withstand current | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V UL certified; 600 V CSA certified; 690 V conforming to IEC 60947-5-1 |
| Mounting support | Plate; Rail |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Operating time | 12...22 ms coil energisation and NO closing; 4...12 ms coil de-energisation and NO opening; 4...19 ms coil energisation and NC opening; 6...17 ms coil de-energisation and NC closing |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Inrush power in VA | 70 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact; 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 84 mm |
| Net weight | 0.58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.200 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.200 cm |
| Package 1 Weight | 349.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.236 kg |
The
control relay CAD32T7 from the
TeSys Deca series by
Schneider Electric is an
auxiliary contactor designed for use in
control circuits. It features a
480 V AC 50/60 Hz coil and is rated for usage categories
AC-15,
AC-14, and
DC-13. The device provides a contact configuration of
3 normally open (NO) and 2 normally closed (NC) contacts, making it suitable for various control tasks in industrial applications. The
screw terminals allow connection with flexible and rigid cables in cross-sections from 1 to 4 mm², with flexible cables with wire end ferrules permitting a cross-section of 1 to 2.5 mm². Mounting is possible either on a
plate or on a
rail, enabling flexible integration into existing control panels.
Applications include controlling auxiliary functions in industrial drives, such as signal transmission, feedback of switching states, or interconnection of control circuits. The relay is designed for demanding operating conditions, especially at high switching frequencies. The maximum operating rate is
180 cycles per minute, corresponding to a total life expectancy of
30 million switching cycles. Mechanical robustness is ensured by vibration and shock resistance according to IEC 60068-2-6 and IEC 60068-2-27, with the device exhibiting up to 15 Gn shock resistance in the closed state.
Functions and equipment in detail include high insulation strength with a
rated impulse withstand voltage of 6 kV as per IEC 60947. The
rated insulation voltage is 690 V according to IEC 60947-5-1, supplemented by certifications for 600 V UL and CSA. The
rated make capacity is 140 A for AC and 250 A for DC, with the associated fuse protection specified as 10 A gG. The
operating time for coil energization and NO contact closing is 12 to 22 ms, while de-energization of the coil and NC contact closing takes 6 to 17 ms. The
non-overlapping time between NO and NC contacts is 1.5 ms, ensuring safe switching operations.
Technology explained simply shows that the relay operates with an
AC coil at 480 V operating voltage. The
pickup power is 70 VA at 50 Hz and the
holding power consumption is 8 VA, ensuring efficient energy use. The
minimum switching voltage is 17 V and the
minimum switching current is 5 mA, ensuring reliability even with weak signals. The
insulation resistance exceeds 10 MΩ, providing high electrical safety. The
ambient temperature during operation ranges from -40 °C to 60 °C, with performance reduction required at temperatures from 60 to 70 °C. The operating altitude is up to 3,000 m above sea level.
Compatibility and accessories include a variety of extensions suitable for adapting to specific requirements. These include
auxiliary switch blocks such as LAD8N11 (1S+1Oe), LADN20 (2S), LADC22 (2S2Oe), or LADN13 (1S3Oe), providing additional contacts.
Time blocks such as LADT2 (0.10–30.00 s) or LADT4 (10.00–180.00 s) enable delayed switching operations.
Interlock blocks such as LAD6K10E (42–48 VAC/DC) or LAD6K10F (110–127 VAC/DC) serve mechanical interlocking.
Protection covers such as LAD9ET1 or LAD9ET1S offer additional front-side protection.
Identification plates such as LA9D92 or LA9D93 facilitate identification.
Mounting and installation is performed by securing to a mounting plate or rail. The screw terminals require a tightening torque of 1.7 Nm, using screwdrivers with Phillips No. 2, flat Ø 6, or position No. 2. Dimensions are 77 mm height, 45 mm width, and 84 mm depth. The product weight is 0.58 kg.
Operational advantages include high mechanical life expectancy, reliability at high switching frequencies, and broad compliance with standards. Certifications include
CB, CCC, UL, CSA, EAC, CE, UKCA, as well as compliance with
RoHS/REACH. The
protection rating IP2x on the front side corresponds to VDE 0106 and protects against finger contact. The coating corresponds to category TH according to IEC 60068, ensuring high resistance to environmental conditions. The operating altitude up to 3,000 m and storage temperature from -60 to 80 °C extend the application range across various climatic and geographic regions.