| Complementary |
| Utilisation category | AC-15; AC-14; DC-13 |
| Pole contact composition | 3 NO + 2 NC |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 440 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| [Icw] rated short-time withstand current | 100 A - 1 s; 120 A - 500 ms; 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V UL certified; 600 V CSA certified; 690 V conforming to IEC 60947-5-1 |
| Mounting support | Rail; Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
| Tightening torque | 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Operating time | 12...22 ms coil energisation and NO closing; 4...12 ms coil de-energisation and NO opening; 4...19 ms coil energisation and NC opening; 6...17 ms coil de-energisation and NC closing |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Inrush power in VA | 70 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA | 8 VA 50 Hz (at 20 °C) |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact; 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 84 mm |
| Net weight | 0.58 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-5-1 |
| Product certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5 cm |
| Package 1 Width | 9.2 cm |
| Package 1 Length | 11.2 cm |
| Package 1 Weight | 350 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.332 kg |
The
control relay CAD32R7 from the
TeSys Deca series by
Schneider Electric is an
auxiliary contactor designed for use in control circuits. It features a
440 V AC 50/60 Hz coil and is rated for usage categories
AC-15,
AC-14, and
DC-13. The device provides a contact configuration of
3 normally closed contacts (NO) and 2 normally open contacts (NC), making it suitable for complex control tasks in industrial systems. The
screw terminals allow connection with flexible and rigid cables in cross-sections from
1 to 4 mm², with the connection method varying depending on cable type and cross-section. Mounting is possible either on a
rail or on a
plate, enabling flexible integration into existing control panels.
Applications include controlling auxiliary functions in industrial machines, plant control systems, and applications requiring high operating speeds. The relay is designed for a maximum operating rate of
180 cycles per minute, corresponding to a total mechanical life of
30 million cycles. The
rated impulse voltage withstand is
6 kV, ensuring reliability during transient voltage surges. The
rated insulation voltage is
690 V according to IEC 60947-5-1, making the device suitable for applications in high-voltage environments. The
rated switching capacity is
140 A for AC and
250 A for DC, highlighting its capability for safe switching under load.
Functions and equipment in detail include a
conventional thermal current rating of 10 A at 60 °C, ensuring thermal stability under load. The
coil power consumption is
70 VA at 50 Hz, while the
holding power consumption is
8 VA, enabling efficient energy use. The
minimum switching voltage is defined as
17 V and the
minimum switching current as
5 mA, ensuring reliability even with weak signals. The
non-overlapping time between normally closed and normally open contacts is
1.5 ms, which is important for precise switching in time-critical applications. The
operating times are
12–22 ms for coil energization and NO closure, and
4–12 ms for coil de-energization and NO opening, ensuring fast responsiveness.
Technology explained simply indicates that the device is designed for operation in a temperature range of
-40 °C to 60 °C, with performance reduction required at temperatures from
60 °C to 70 °C. The
operating altitude is limited to
0 to 3,000 m above sea level.
Mechanical robustness is confirmed by shock and vibration tests according to IEC 60068-2-27 and IEC 60068-2-6, with the device exhibiting
10 Gn shock resistance in open state and
15 Gn in closed state. The
insulation resistance is specified as
> 10 MΩ, ensuring high electrical insulation. The
coating corresponds to category
TH according to IEC 60068, enhancing resistance to environmental influences.
Compatibility and accessories include use with various auxiliary switch blocks such as
LADN13 (1S3Ö),
LADN22 (2S+2Ö),
LADN40 (4S), or
LADN10 (1S), which extend the number of contacts. Interlocking blocks such as
LAD6K10F (110–127 VAC/DC) or
LAD6K10M (220/240 V AC/DC) enable mechanical interlocking with other relays. Time delay blocks such as
LADR0 (0.10–3.00 s) or
LADR2 (1–30.00 s) allow integration of time delay functions.
Protection covers such as
LAD9ET1S or
LAD9ET1 provide additional protection for contacts.
Identification plates LA9D92 and
LA9D93 are used for marking terminals.
Mounting and installation is performed using the provided mounting brackets on a rail or plate. The
torque values for the screw terminals are
1.7 Nm, and mounting can be done using a Phillips screwdriver No. 2, a flat screwdriver Ø 6, or a positioning screwdriver No. 2. The
protection rating is
IP2x on the front according to VDE 0106, providing protection against finger contact but not against dust or water. The
certifications include
CB, CCC, UL, CSA, EAC, CE, UKCA, ensuring international usability of the device.
Compliance with standards is according to
EN/IEC 60947-5-1,
GB/T 14048.5,
UL 60947-5-1,
CSA C22.2 No. 60947-5-1, and
JIS C8201-5-1.
Operational advantages include high mechanical life, fast switching speed, and reliability at high operating rates.
RoHS/REACH compliance ensures environmental compatibility. The
rated short-time current withstand of
100 A (1 s), 120 A (500 ms), 140 A (100 ms) ensures stability during short-term overloads. The
rated insulation voltage of
690 V and
impulse voltage withstand of
6 kV enhance safety in electrical installations. The
associated fuse rating is specified as
10 A gG, enabling correct dimensioning of protective measures. The device is designed for use in industrial environments with high requirements for reliability and service life.